2-8. E: 33. Indoor unit motor electricity consumption detection
error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 33
Detective actuator
Indoor unit motor electricity
consumption detection
When the voltage value or the current value of the motor
go beyond the limits
Forecast of cause
Fan motor failure
Main PCB failure
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in
03-49.)
→ If indoor unit fan motor is abnormal, replace it.
↓
Check point 4. Replace main PCB
If check point 1-3 does not improve the symptom, change main PCB.
↓
End
2-8. E: 33. Indoor unit motor electricity consumption detection error (Indoor unit)
- (03-13) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...