AIR CONDITIONER

OPTIONAL PARTS

External connect kit

PART NO. 9319446004

INSTALLATION MANUAL

For authorized service personnel only.

1.  SAFETY PRECAUTIONS

 

WARNING

This mark indicates procedures which, if improperly performed, 

might lead to the death or serious injury of the user.

When installing each wire, please thoroughly read this manual.
Before installation be sure that all sources of power have been shut off. 

There is a danger of electric shock.
For input/output, use the voltage as described in the signal specifications. 

Using voltage of other specifications may result in malfunction and erroneous operation 

of the airconditioner.

 CAUTION

This mark indicates procedures which, if improperly performed, 

might possibly result in personal harm to the user, or damage 

to property.

Do not pull on the connectors with too much force.

2.  ABOUT THE UNIT

2. 1.  Main Unit & Accessories

• The following installation parts are supplied. Use them as required.

Name and Shape

Q’ty

Application

Installation  

manual

1

This manual

Wire (External input): 

Orange / Yellow

1

For connect to External device for 

input.

Wire (External output): 

Blue / Purple

1

For connect to External device for 

operation status output.

Wire (External output): 

Red / White

1

For connect to External device for 

error status output.

Binder clamp 

1

For fixing the binder.

Binder

1

For fixing the wires.

Screw

1

For fixing the binder clamp.

3.  SETTING

3. 1.  External Input

3. 1. 1. Control Input (Operation/Stop or Forced stop)

• The air conditioner can be remotely operated by means of the following on-site work. 

"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of 

indoor unit.

Circuit diagram example

 

Indoor unit

PC board of 

communication kit

Connector

Orange

Yellow

Connected unit

Ex.) Switch

10m *

Signal

Field supply

* Make the distance from the PC board to the connected unit within 10m.

Contact capacity : 24VDC or more, 10mA or more.

● When function setting is "Operation/Stop" mode

Input signal

Indoor unit

OFF

Stop

ON

Operation

● When function setting is "Forced stop" mode

Indoor unit

Input signal

Command

Remote controller

Remote control operation invalidity

Normal

Stop

OFF

Forced stop

Operation

ON

ON

ON

ON

NOTE

• Operation mode, temperature, and airflow cannot be set by external input. Use the 

remote controller to set.

• If the air conditioner is activated by external input, it will operate in the settings before 

stop. To change the settings, use the remote controller.

9319446004_UTY-XWZXZ5_IM.indd   1