- Continued on back -
SPLIT TYPE AIR CONDITIONER
Ceiling Suspension Type
INSTALLATION MANUAL
(PART NO. 9361156012-02)
For authorized service personnel only.
WARNING
SELECTING THE MOUNTING POSITION
WARNING
CAUTION
CAUTION
Hold the torque wrench at its grip, keeping it in the right
angle with the pipe as shown in Fig. 25, in order to tighten
the flare nut correctly.
CAUTION
Be sure to apply the pipe against the port on the indoor
unit correctly. If the centering is improper, the flare nut
cannot be tightened smoothly. If the flare nut is forced to
turn, the threads will be damaged.
WARNING
CAUTION
In order to check the drainage, be sure to use a level dur-
ing installation of the indoor unit. If the installation site of
the indoor unit is not level, water leakage may occur.
WARNING
Install the unit where it will not be tilted by more
than 5
°
.
When installing the outdoor unit where it may
exposed to strong wind, fasten it securely.
(1)
(2)
(1)
(2)
Install the unit where it will not be tilted by more than 5
°
.
When installing the outdoor unit where it may exposed to
strong wind, fasten it securely.
The maximum lengths of this product are shown in table 3.
If the units are further apart than this, correct operation
can not be guaranteed.
CAUTION
(1)
For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
(2)
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(3)
Do not turn on the power until all installation work is complete.
•
Be careful not to scratch the air conditioner when handling it.
•
After installation, explain correct operation to the customer, using the operating manual.
•
Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved.
Install at a place that can withstand the weight of the
indoor and outdoor units and install positively so that
the units will not topple or fall.
Do not install where there is the danger of com-
bustible gas leakage.
Do not install the unit near a source of heat, steam,
or flammable gas.
If children under 10 years old may approach the unit,
take preventive measures so that they cannot reach
the unit.
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
Install the indoor unit level on a strong wall which is not subject to
vibration.
The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room.
Do not install the unit where it will be exposed to direct sunlight.
Install the unit where connection to the outdoor unit is easy.
Install the unit where the drain pipe can be easily installed.
Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 2 or 3). Also install the unit where the filter can be removed.
(1)
(2)
(3)
2. OUTDOOR UNIT
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INSTALLATION PROCEDURE
Install the air conditioner as follows:
Name and Shape
Q’ty
Application
Remote
control unit
1
1
2
1
Drain hose insulation
3
Adhesive type 70
×
230
Remote
control
unit holder
1
Tapping screw
(ø3 x 12)
For remote control unit
holder installation
Battery (penlight)
4
Coupler heat insulator (large)
For indoor side pipe joint
(large pipe)
Large
4
Small
4
Nylon fastener
Auxiliary pipe assembly
For fixing the coupler heat
insulator
1
For connecting the piping
Special nut B
(small flange)
4
For installing indoor unit
Special nut A
(large flange)
4
For installing indoor unit
VT wire
For fixing the drain hose
L 280 mm
1
Coupler heat insulator (small)
For indoor side pipe joint
(small pipe)
1
Installation
template
For positioning the indoor
unit
Diameter
Large
Small
5/8”(ø15.88 mm)
3/8”(ø9.53 mm)
INDOOR UNIT ACCESSORIES
CONNECTION PIPE REQUIREMENT
•
Use 0.7 mm to 1.2 mm thick pipe.
•
Use pipe with water-resistant heat insulation.
•
Electric wire size and fuse/breaker capacity:
INDOOR UNIT INSTALLATION
PREPARING INDOOR UNIT
INSTALLATION
You can use the accessory template to help you install the indoor
unit. The template helps you determine the appropriate locations for
suspension bolts and pipe openings (drain pipe and connection cord).
Fig. 6
1. LOCATION OF CEILING SUSPENSION BOLTS
Fig. 7
[For Half-Concealed Installation]
Suspension-bolt pitch should be as shown in Fig. 7.
Fig. 8
2. SELECT PIPING DIRECTION.
Select connection piping and drain piping directions (Fig.9).
Fig. 9
[For
4
Left rear piping,
5
Left piping]
Transfer the Drain cap and Drain cap seal.
Fig. 10
DRILLING THE HOLES AND ATTACHING THE SUS-
PENSION BOLTS
Drill ø25mm holes at the suspension-bolt locations.
Install the bolts, then temporarily attach Special nuts A and B
and a normal M10 nut to each bolt. (The two special nuts are pro-
vided with the unit. The M10 nut must be obtained locally.) Refer
to Fig. 11.
Fig. 11
[If using anchor bolts]
Drill holes for anchor bolts at the locations at which you will set
the suspension bolts. Note that anchor bolts are M10 bolts (to be
obtained locally).
Install the anchor bolts, then temporarily attach special nut "B"
(included) and a locally-procured M10 nut to each of the bolts.
(See Fig. 12.)
Fig. 12
4. INSTALLING THE INDOOR UNIT
Lift unit so that suspension bolts pass through the suspension fit-
tings at the sides (four places), and slide the unit back. (See Fig.
14.)
Fig. 13
Fig. 14
Fasten the indoor unit into place by tightening-up the special “B”
bolts and the M10 nuts. Make sure that unit is secure and will not
shift back and forth.
[For Half-Concealed Installation]
When installing the indoor unit in a semi-concealed orientation, make
sure to reinforce the insulation of the unit on all sides. Drops of water
may fall from the unit if it is not thoroughly insulated.
Fig. 15
2. FLARE PROCESSING
Cut the connection pipe with pipe cutters so that the pipe is not
deformed.
Holding the pipe downward so that cuttings cannot enter the pipe,
remove the burrs.
Remove the flare nut from the indoor unit pipe and outdoor unit
and assemble as shown in (Table 4) and insert the flare nut onto
the pipe, and flare with a flaring tool.
Check if the flared part “L” (Fig. 19) is spread uniformly and that
there are no cracks.
Table 4
(1)
(2)
(3)
(4)
CONNECTING THE PIPING
Fig. 2
[FOR HALF CONCEALED INSTALLATION]
Fig. 3
Fig. 1
If possible, do not install the unit where it will exposed to direct
sunlight. (If necessary, install a blind that does not interfere with the
air flow.)
Install the outdoor unit in a place where it will be free from being dir-
ty or getting wet by rain as much as possible.
Install the unit when connection to the indoor unit is easy.
During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed. (Heat & Cool model (Reverse cycle) only)
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where
noise and vibration are small.
Select a place so that the warm air and noise from the air conditioner
do not disturb neighbors.
Provide the space shown in Fig. 4 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
Fig. 4
Table 1
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Use for air conditioner
operation
For remote control unit
For mounting the remote
control unit
Power supply cord (mm
2
)
Connection cord (mm
2
)
MAX
MIN
MAX
MIN
3.5
3.0
1.5
1.0
Fuse/Breaker capacity (A)
30
ELECTRICAL REQUIREMENT
•
•
Always use H07RN-F or equivalent as the cord.
Install the disconnect device with a contact gap of at least 3 mm
nearby the units. (Both indoor unit and outdoor unit)
Table 2
(1)
(2)
(3)
(4)
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
REMOVE THE INTAKE GRILLE AND SIDE COVER.
Remove the two Air filters (Fig.5).
Remove the two Intake grilles (Fig.5).
For
4
Left rear drain and
5
Left drain: Remove air filters and
intake grilles at three places. (Refer to "
2
INDOOR UNIT
INSTALLATION".)
Remove the Side cover A (Right side) and Side cover B (Right
and Left side).
For
5
Left drain : Remove both the Side cover A (Right and
Left side). (Refer to "
2
INDOOR UNIT INSTALLATION".)
This air conditioner can be set up to intake fresh air. For informa-
tion about how to install for fresh-air intake, refer to "
E
FRESH-
AIR INTAKE".
Fig. 5
•
•
•
•
•
Anchor-Bolt Strength
980 to 1470 N (100 to 150 kgf)
Bolt Strength
980 to 1470 N (100 to 150 kgf)
Pipe
Small pipe
Large pipe
Flare nut
Small (width across flats 22 mm)
Large (width across flats 24 mm)
(1)
(2)
(3)
(4)
(5)
(6)
3.
Do not bend the pipes in an angle less than 90
°
.
When the pipes are bent and stretched repeatedly, the material will be
hardened, causing the pipes no longer be sent or stretched. Be sure to lim-
it number of bending and stretchings to three times.
When bending the pipe, do not bend
it as is. The pipe will be collapsed. In
this case, cut the heat insulating pipe
with a sharp cutter as shown in Fig.
21, and bend it after exposing the
pipe. After bending the pipe as you
want, be sure to put the heat insulat-
ing pipe back on the pipe, and secure
it with tape.
4. CONNECTION PIPES
[Indoor unit side]
Remove the filter guide (Fig. 22).
Fig. 22
Attach the connection pipe. (Fig. 23)
Fig. 23
For
2
Top piping and
3
Right piping connections, use the Aux-
iliary pipe (large pipe) provided.
Fig. 24
When the flare nut is tightened properly by your hand, hold the boby side
coupling with a separate spanner, then tighten with a torque wrench. (Fig. 25)
Fig. 25
Table 5 : Flare nut tightening torque
[Outdoor unit side]
Tighten the flare nut of the connection pipe at the outdoor unit valve
connector. The tightening method is the same as that as at the indoor
side.
Fig. 26
Fig. 21
Hexagon wrench
1
For opening the refrigerant
valve on the outdoor unit
For power cord binding
Cable clip
2
1
For outdoor unit drain
piping work
[Heat & Cool (Reverse cycle)
model only]
Drain pipe
1
Drain cap
2
OUTDOOR UNIT ACCESSORIES
For fixing the valve cover
Tapping screw
(painted)
OUTDOOR UNIT INSTALLATION
1. OUTDOOR UNIT PROCESSING
When the outdor unit will be exposed to strong wind, fasten it with
bolts at the places indicated by the arrows. (Fig. 16)
Fig. 16
(1)
(2)
If this product is used in an area where
the temperature falls below freezing
for long periods of time, do not con-
nect the drain pipe. Instead, allow the
water to drain into a drain pan.
CAUTION
2. OUTDOOR UNIT CONNECTION CORD AND
PIPE CONNECTION PREPARATIONS
Remove outdoor unit valve cover.
Fig. 17
Connect the piping, connection cord and power cord.
Fig. 18
Set the unit on a strong stand, such as one mode of concrete blocks to
minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
•
•
99 ft (30 m)
82 ft (25 m)
49 ft (15 m)
1. LIMITATION OF REFRIGERANT PIPING LENGTH
Table 3
Cooling model
Heat & Cool model
(Reverse cycle)
Max length (L)
Max height difference (H)
Fig. 19
3. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 20
Pipe
Small pipe
(9.53 mm dia.)
Large pipe
(15.88 mm dia.)
Tightening torque
310 to 350 kgf
•
cm (30.4 to 34.3 N
•
m)
750 to 800 kgf
•
cm (73.5 to 78.4 N
•
m)
1
4
3
2
Tapping screw
Air filter
Intake grille
Side cover B
(Left side)
INDOOR UNIT
Side cover A (Right side)
Side cover B (Right side)
INDOOR UNIT
Suspension bolt pitch 1600 mm
INDOOR UNIT (TOP VIEW)
30 mm
30 mm
Dimensions
(Space Required for
Installation)
Suspension bolt should
extend outward 30 to 75mm.
10 mm
155 mm
300 mm
Ceiling Opening: 1580mm
40 mm
40 mm
Ceiling panel
Ceiling Opening: 640mm
15 mm
Ceiling panel
Suspension bolt should
extend outward 30 to 50mm.
INDOOR UNIT
1
Right rear piping
2
Top piping
(Connection pipe only)
3
Right
piping
4
Left rear piping
(Drain pipe only)
5
Left piping
(Drain pipe only)
INDOOR UNIT (TOP VIEW)
Cut off the piping outlet cutting groove
with a hacksaw, etc.
Wall
Ceiling
M10 Anchor Bolt
(Obtained locally)
Ceiling
10 to 15 mm
Special nut B
(Included)
M10 Nut
(Obtained locally)
M10 Nut (Obtained locally)
10 to 15 mm
Special nut A (Included)
Ceiling panel
Special nut B (Included)
L dimension
Small pipe (9.53 mm dia)
1.8 to 2.0 mm
Large pipe (15.88 mm dia)
2.2 to 2.4 mm
Ceiling panel
3” (80 mm)
or over
INDOOR UNIT
6” (150 mm)
or over
Ceiling panel
0.4” (10 mm)
or over
Drilling position for piping
Drilling position for Suspension bolt
Ceiling
Wall
Template
Push cap all the way on
(as far as it will go).
Drain cap
Drain cap seal
Indoor unit
Drain pan
Drain cap seal
Drain cap
Wall
INDOOR UNIT
Ceiling panel
Ceiling
INDOOR UNIT
3” (80 mm)
or over
Ceiling
6” (150 mm)
or over
0.4” (10 mm)
or over
2
Top piping
3
Right piping
Large pipe
Large pipe
Auxiliary pipe (large pipe)
Indoor unit (rear)
Filter guide
Indoor unit
INDOOR UNIT
(Top view)
Wall
Ceiling panel
Glass wool insulate
(10 to 20mm thick)
Small pipe
Indoor unit
Large pipe
24” (600 mm)
or more
AIR
12”
(300 mm)
or more
12”
(300 mm)
or more
12”
(300 mm)
or more
24” (600 mm)
or more
31-21/32” (804 mm)
Drain pipe mounting hole
Bottom plate
Drain pipe
3/4” (19 mm)
13-7/64”
(333 mm)
Air flow
Drain cap
Bottom
Valve cover
take off direction
* After removing the screws,
remove valve cover
Valve cover
Valve
Pipe
Power cord
Connection
cord
(Small pipe)
(Large pipe)
Connection pipe
Flare nut
2-way valve
3-way valve
INDOOR UNIT
OUTDOOR UNIT
Connection cord
1.0 to 1.5 mm
2
(H07RN-F or equivalent)
Drain pipe
VP25 (General polyvinyl chloride pipe)
5/8” (ø15.88 mm)
3/8” (ø9.53 mm)
Power supply cord
3.0 to 3.5 mm
2
(H07RN-F or equivalent)
Power supply
1ø
•
220-240V
•
50Hz
Special branch circuit breaker
(Fuse/Breaker capacity : 30A)