Soft Start OUT1 Output
,
Soft Start Time
This function controls the maximum output produced
when turning on the equipment (including the temperature
controller).
The controls place an upper limit on the output for a set time
period after the power is turned on.
This function is useful for effects such as suppressing the
heater output during equipment startup, or lightening the load.
After the specified time has passed after switching on the
equipment (or if SFTM = 0), the soft start function ends and
normal controls begin.
Setting Soft Start OUT1 Output/OUT1 Time
This section explains how to set soft start output and time by
using output = 5% and time = 30 min. as an example.
Parameter
Function
SFo1
OUT1 set value
OUT1 is limited for the time period specified in
SFTM after the power is turned on.
SFo2
OUT2 set value
OUT2 is limited for the time period specified in
SFTM after the power is turned on.
* This is used when there are dual outputs.
SFTM Set Time
(unit: hh, mm)
Sets the time for soft start to function after
turning power on.
Setting "0" will turn off soft start.
Point
During manual mode, the manual output value has priority,
but soft start will continue to keep track of the set time period.
Caution
The soft start function cannot be used when there are dual
outputs.
Do not use self-tuning during soft start. The soft start may not
be controlled correctly.
t
control output (MV)
soft start
set time
soft start
output set
value
MV before soft start
MV with soft start
(limited)
power
on
0%
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to display SFo1 ("
SSS
SFFFFoooo1111
").
3
Press the
key, then use the
keys to
select 5.0 when the bottom part of the display
begins to blink.
The OUT1 soft start output is set to 5%.
4
Press the
key to confirm the setting.
5
Repeat steps 2 to 4 (excluding pressing and holding
the
key) to set OUT2.
6
Use the
keys to select "
SSS
SFFFFTTTTMMMM
".
7
Press the
key, then use the
keys to
select 0.30 when the bottom part of the display
begins to blink.
Soft start time is set to 30 min.
8
Press the
key to return to the operation
mode PV/SV display.
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...