![FujiFilm PXG4 Скачать руководство пользователя страница 75](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483075.webp)
– 74 –
8
Chapter
PV Input Types
PV input source can be any of the following, including
thermocouples and resistance thermometer bulbs.
Setting the PV Input Type
This section explains how to change the PV input type with
the example of changing from the factory thermocouple
setting of K to R.
Setting
Input Type
Sensor Type
0
JPT 100
Ω
Resistance thermometer bulb
1
PT100
Ω
2
J
Thermocouple
3
K
4
R
5
B
6
S
7
T
8
E
9
No function
10
No function
11
No function
12
N
13
PL-II
14
Reserved
15
0V to 5V/0-20mA
Voltage/Current Input
16
1V to 5V/4-20mA
17
0V to 10V
Voltage Input
18
2V to 10V
19
0mA to 100mV
Caution
• When changing between current input (0-20mA/4-20mA)
and voltage input (0-5V/1-5V), remove the 250
Ω
resistor
connected to the terminal block. (Or vice versa.)
• Different types of input (thermocouple/resistance thermometer
bulb/voltage or current input) require different connections to
the terminal block. Check the "Instruction Manual".
1
Press and hold the
key to display "
MMM
Mvvvv1111
".
The MV1 of the monitoring mode is displayed.
2
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Specify the PV input type.
3
Press and hold the
key, then use the
keys to display PvT ("
PPP
PvvvvTTTT
").
4
Press the
key, then use the
keys to
select 4 when the bottom part of the display
begins to blink.
The PV input type is “R thermocouple".
5
Press the
key to confirm the setting.
6
Press the
key to return to the operation mode
PV/SV display.
Operation mode
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...