Chapter
Overview of Setup Parameters (Ch6)
This section covers the analog input and output of this device.
This section applies to the following types of input:
• PV(Input from sensors such as thermocouples and resistance thermometer bulbs)
• RSV(Remote SV input)
• OUT1/OUT2 (Current/Voltage control output)
• AO (Re-transmission Output)
Display
Parameter name
Function
Setting range
Initial value
Remarks
Reference
Page
"
PvT
" (PvT)
PV input type
Sets the type of input sensor
0 (JPT 100
Ω
)
1 (PT 100
Ω
)
2 (J)
3 (K)
4 (R)
5 (B)
6 (S)
7 (T)
8 (E)
9 (no function)
10 (no function)
11 (no function)
12 (N)
13 (PL-
2
)
14 (no function)
15 (0V to 5V/0mA to 20mA)
16 (1V to 5V/4mA to 20mA)
17 (0mV to 10V)
18 (2V to 10V)
19 (0mV to 100mV)
3 (K)
74
"
Pvb
" (Pvb)
PV input lower limit
Sets a lower limit for PV input
-1999% to 9999%
0%
75
"
PvF
" (PvF)
PV input upper limit
Sets the upper limit for PV input
-1999% to 9999%
400°C
"
Pvd
" (Pvd)
Decimal position
Sets the position of the decimal point
for PV/SV display
0 (no decimal point)
1 (one decimal place)
2 (two decimal places)
0
75
"
PvU
" (PvU)
Unit display
This is the procedure for specifying
the units of the PV/SV display.
°C/°F
°C
—
"
PvoF
" (PvoF)
PV input shift
Sets the amount of shift for PV input
0% to 100% FS
0%
76
"
SvoF
" (SVoF)
SV offset
Sets the amount of shift in SV
-50% to 50% FS
0%
76
"
TF
" (TF)
PV input filter
Sets the time constant for the PV
input filter
0.0 sec to 120.0 sec
5.0sec
77
"
AdJ0
" (AdJ0)
PV display Zero
adjustment
Adjusts the zero side in the PV
display
-50% to 50% FS
0%
78
"
AdJS
" (AdJS)
PV display Span
adjustment
Adjusts the span side in the PV
display
-50% to 50% FS
0%
"
rCJ
" (rCJ)
Cold Junction
Compensation
Sets whether cold junction
compensation is performed
oFF (Off)/on (On)
on
79
"
rEMO
" (rEMO)
RSV Zero
adjustment
Adjusts zero side in RSV input
-50% to 50% FS
0%
Note 1
80
"
rEMS
" (rEMS)
RSV Span
adjustment
Adjusts the span side of RSV input
-50% to 50% FS
0%
Note 1
"
rEMr
" (rEMr)
RSV Input Range
Specifies the RSV input range
0-5 (0mA to 5V)
1-5 (1V to 5V)
1-5v
Note 1
81
"
rTF
" (rTF)
RSV Input Filter
Sets the time constant for the RSV
input filter
0.0 sec to 120.0 sec
0.0 sec
Note 1
82
"
C1r
" (C1r)
OUT1 range
Sets the range of the control output
(OUT2)
0-5 (0mA to 5V)
1-5 (1V to 5V)
0-10 (0mA to 10V)
2-10 (2V to 10V)
0-20 (0mA to 20mA)
4-20 (4mA to 20mA)
0-10
(Voltage)
4-20
(Current)
Note 2
Note 3
83
RST
RST
RST
RST
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...