Operation parameters handle all operation controls.
The operation menu includes the following items.
Note 1: Displays when the seventh digit of the model code is H, K, F, 2 or E, or the eleventh digit is D.
Note 2: Displays when the ninth digit of the model code is not 0, or the eleventh digit is C.
Note 3: The range of the parameters in the shaded area indicates the industrial values.
Note 4: When changing the SV value with the front panel key, do not change the "
Svn
" parameter with communication. The
changed SV value may not be stored correctly.
Display
Parameter name
Function
Setting range
Initial
value
Remarks
Page
"
Man
" (Man)
Switches to manual
mode
Switches between auto/manual
modes
oFF (off)/on (manual)
oFF
23
"
STbY
" (STbY)
Switches between
RUN and standby
Switches the operation mode
between run and standby
oFF (off)/on (standby)
oFF
24
"
rEM
" (rEM)
Switches to remote
SV operation
Switches between local and
remote SV operation
LoCL (Local)/
rEM (Remote)
LoCL
(Note 1)
24
"
PrG
" (PrG)
Ramp/Soak
Operation
command
Switches between ramp/soak
operation states
oFF (stop)
rUn (run)
hLd (hold)
oFF
Displays End
when finished,
and GS during
guaranteed soak.
25
"
AT
" (AT)
Auto-tuning
running command
Runs auto-tuning.
oFF (stop/finish)
on (normal type)
Lo (low PV type)
oFF
25
"
LACH
" (LACH)
Cancel command of
the DO output latch
Cancels the DO output latch state
oFF/ rST
(latch reset)
oFF
(Note 2)
26
"
Svn
" (Svn)
Selecting SV
number during
SV selection
Chooses the SV No. used for
control
Sv0 (Local SV)
Sv1 (SV=SV1)
Sv2 (SV=SV2)
Sv3 (SV=SV3)
Sv4 (SV=SV4)
Sv5 (SV=SV5)
Sv6 (SV=SV6)
Sv7 (SV=SV7)
di (select SV based on di)
Sv0
(Note 4)
26
"
PLn1
" (PLn1)
Currently selected
PID No.
Chooses the PID group No. used
for control
Pid0 (PID Ch)
Pid1 (PID group No. 1)
Pid2 (PID group No. 2)
Pid3 (PID group No. 3)
Pid4 (PID group No. 4)
Pid5 (PID group No. 5)
Pid6 (PID group No. 6)
Pid7 (PID group No. 7)
di (select Pid group No.
based on di)
Pid0
27
"
AL1
"
"
AL1l
"
"
AL1h
"
"
AL5
"
"
AL5l
"
"
AL5h
"
AL1 Setting
AL1L Setting
AL1h Setting
AL5 Setting
AL5L Setting
AL5h Setting
Sets the alarm set value.
0 to 100% FS
(Absolute Alarm)
-100 to 100% FS
(Deviation Alarm)
10%
(Note 3)
27
"
LoC
" (LoC)
Key lock
Sets the key lock to prevent
operation errors
0 (no lock)
1 (all lock)
2 (all but SV locked)
0
28
…
…
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...