Delay Start Function
Ramp soak can be automatically started (RUN) after a certain
period of time has elapsed since the power of the controller is
turned on.
This function is enabled by setting the digital input function
(DI n) and the digital output function (DonT), and the delay
time can be set with dLYn.
The delay start function is enabled by setting di1-5, do1T-
do5T(SYS Ch7), dLY1-5, and dL1U-dL5U (ALM Ch8).
Setting range of each parameter when enabling delay start:
di1 to di5
: 44 to 48
do1T to do5T
: 35
dLY1 to dLY5
: 0 to 9999
dL1U to dL5U
: Min/Sec
Setting MOD (PrG Ch4) or SbMd (SET Ch 6) can realize the
following operation.
To have the unit operate as in the figure above, configure the
settings as follows:
Mod
: 6
StMd
: 1
This figure sets the PTn (PrG Ch4) to 0, but any value can be
set for the PTn to realize the similar operation.
Setting the Delay Start Function
The following steps will explain how to assign the delay start
to DI 2, Do2 and to set the delay time to 15 minutes.
*
For the detailed setting for each parameter, see the
setting procedure for each parameter.
1st ramp
SV-1
2nd ramp
3rd ramp
4th ramp
SV-2
SV-3
SV-4
TM4S
TM4r
TM3S
TM3r
TM2S
TM2r
TM1S
TM1r
dLYn
dLYn
TM1r
TM1S TM2r TM2S TM3r TM3S TM4r
TM4S
Temperature
control stop
Temperature control
Temperature control stop
1st ramp
2nd ramp
3rd ramp
4th ramp
Ramp soak END state
SV-
1
SV-2
SV-3
SV-4
1
Display the system menu (
SSS
Syyyyssss CCCChhhh7777
).
2
Display the Di2 function selection ("
ddd
diiii2222
"), and set
45 ("
444
45555
").
3
Display the DO2 output event type setting
("
ddd
doooo2222TTTT
"), and set 35 ("
333
35555
").
4
Display the Alarm (
AAA
ALLLLMMMM CCCChhhh8888
).
5
Display the ALM2 delay time ("
ddd
dLLLLYYYY2222
"), and set 15
("
111
15555
").
6
Display the ALM2 delay time unit ("
ddd
dLLLL2222UUUU
"), and
set the minute ("
MMM
Miiiinnnn
").
7
Press the
key to return to the operation mode
PV/SV display.
Содержание PXG4
Страница 1: ...c...
Страница 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Страница 21: ...20 MEMO 2 Chapter...
Страница 43: ...42 MEMO 4 Chapter...
Страница 53: ...52 MEMO 5 Chapter...
Страница 71: ...70 MEMO 7 Chapter...
Страница 89: ...88 MEMO 8 Chapter...
Страница 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Страница 119: ...118 MEMO 10 Chapter...
Страница 125: ...124 MEMO 11 Chapter...
Страница 131: ...130 MEMO 12 Chapter...
Страница 132: ...131 13 Chapter Chapter 13 Password Setup Ch11 Overview of Password Setup Ch11 132 Passwords 1 to 3 132...
Страница 141: ...140 MEMO 14 Chapter...
Страница 151: ...150 MEMO 15 Chapter...
Страница 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Страница 154: ...153 17 Chapter Chapter 17 Appendix Delay Start Function 154 Return to Factory Default Setting Function 155...
Страница 157: ...156 MEMO 17 Chapter...