1. Specifications
1-1. Indoor unit
Type
Cassette
Inverter heat pump
Model name
AUXG18KRLB
AUXG22KRLB
Power supply
230 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
5.2
6.0
Btu/h
17,700
20,500
Min.—Max.
kW
0.90—5.40
0.90—6.30
Btu/h
3,100—18,400
3,100—21,400
Heating
Rated
kW
6.0
7.0
Btu/h
20,500
23,900
Min.—Max.
kW
0.90—6.30
0.90—7.40
Btu/h
3,100—21,400
3,100—25,200
Input power
Cooling
Rated
kW
1.60
1.85
Max.
2.33
2.67
Heating
Rated
1.66
1.93
Max.
2.33
2.67
Current
Cooling
Rated
A
7.4
8.2
Heating
7.7
8.5
Power factor
Cooling
%
94.0
98.1
Heating
93.7
98.7
EER
Cooling
kW/kW
3.25
3.24
COP
Heating
3.61
3.63
Moisture removal
L/h (pints/h)
1.5 (2.6)
2.2 (3.9)
Maximum operating current *1
Cooling
A
10.1
11.6
Heating
10.1
11.6
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,050
MED
960
LOW
900
QUIET
780
Heating
HIGH
1,050
MED
960
LOW
900
QUIET
780
Type × Q'ty
Turbo fan × 1
Motor output
W
81
Sound pressure level *2
Cooling
HIGH
dB (A)
33
MED
32
LOW
31
QUIET
28
Heating
HIGH
33
MED
32
LOW
31
QUIET
28
Heat exchanger type
Dimensions (H × W × D)
mm
Main 1: 210 × 2,127 × 13.3
Main 2: 210 × 2,061 × 13.3
Fin pitch
Main 1: 1.2
Main 2: 1.2
Rows × Stages
Main 1: 1 × 10
Main 2: 1 × 10
Pipe type
Copper tube
Fin type
Aluminum
Dimensions
(H × W × D)
Net
mm
246 × 840 × 840
Gross
298 × 960 × 950
Weight
Net
kg
23
Gross
28
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas
Ø 12.70 (Ø 1/2)
Method
Flare
Drain hose
Material
PVC(VP25)
Size
mm
Ø 25 (I.D.), Ø 32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Cassette grille
(Option)
Material
Polystyrene
Color
White
Approximate color of MUNSELL N 9.25/
Dimensions
(H × W × D)
Net
mm
53 × 950 × 950
Gross
110 × 1,000 × 1,010
Weight
Net
kg
6.0
Gross
10.0
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-1) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Содержание AOYG18KATA
Страница 3: ...CONTENTS 1 GENERAL INFORMATION 2 TECHNICAL DATA AND PARTS LIST ...
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 10 01 SR_CH01_AU012EF_02 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2019 10 01 SR_CH02_AU012EF_02 ...