Step 7: Refer to the table below to size air line conduit. Set conduit in prepared trench (min. 6”
deep) from tank to air pump.
16
Air Line Conduit Diameter Table. (For conduit runs with fewer than 5 elbows)
FujiClean Model/
Air Pump Size
Air Pump to Tank
Distance
CE5, CE7
CEN5
/
FujiMAC
80RII
CE10,
CEN7
/
FujiMAC
100RII
CE14,
CEN10
/
FujiMAC
150RII
CE21,
CEN14
/
FujiMAC
200RII
CE30,
CEN21
/
FujiMAC
150RII (2)
<33 feet
3/4”
3/4”
3/4”
3/4”
1”
<100 feet
1”
1”
1”
1”
1”
Note: Air pump connection
piping does not count
toward “5-elbow” limit
3/4” or 1” PVC conduit
※
If site conditions prevent these parameters from being followed, please consult with FujiClean USA for possible air pump upsize.
Note: Some states and contractors require
a flexible air line adaptor as shown.
(adaptors supplied by FujiClean USA)
Air line / Air Pump
configuration for some
FujiClean models
¾”
¾”
1”
Air Line Connection to Air Pump(s) – Commercial System Examples