10. Electrical characteristics
Model name
ROG07KMTA
ROG09KMTA
ROG12KMTA
ROG14KMTA
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
9.0
Starting current
A
3.0
3.4
5.1
6.8
Wiring
spec. *2
Circuit breaker current
A
15
Power cable
mm
2
1.5
Connection
cable *3
Cross-
sectional
area
mm
2
1.5
Limited
wiring
length
m
21
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri-
ate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor
size.