![Fuji Electric OPC-PRT Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/fuji-electric/opc-prt/opc-prt_instruction-manual_2341941052.webp)
51
8 FIRMWARE
8.1
Overview
The interface card’s embedded firmware can be updated in the field. Firmware updates may be released
for a variety of reasons, such as custom firmware implementations, firmware improvements and added
functionality as a result of user requests. Additionally, it may be necessary to load different firmware onto
the unit in order to support various protocols. In order to ensure that the firmware update is successful,
and in the interest of equipment and personnel safety, it is strongly recommended to stop all of the
card’s production activities prior to initiating the firmware update procedure.
Failure to follow the firmware update procedure could result in corrupt firmware!
8.2
Update Procedure
1.
Always back up your configuration to a PC for later recovery if necessary.
2.
Download and install the latest Configuration Studio, which can be obtained from the
3.
Please be sure to read the firmware release notes and updated user’s manual for any important
notices, behavior precautions or configuration requirements prior to updating your firmware.
4.
Ensure that the device is in a safe state prior to initiating the firmware update. The card may be
temporarily inaccessible during the firmware update process.
5.
Locally via USB:
Connect a USB cable between the card and the PC and open the studio. If the
studio contains newer firmware, it will automatically prompt you to update the firmware. Proceed
with the firmware update.
6.
Remotely Via FTP:
Connect an Ethernet cable and ensure that the card has compatible network
settings.
7.
Once the firmware update process has started, do not interrupt the card as this may corrupt the
firmware. Do NOT manually power-cycle the inverter or reboot the card. Do NOT disturb the USB
or Ethernet (FTP) connection.
8.
After the firmware update has been completed, the card will reset automatically. When the card
boots up again, it will be running the new application firmware, which can be confirmed by
observing the version displayed in
Device…Device Info
or the web server’s information window
(refer to section 6.2.1).
9.
If new default web server content is available, load the new web server (refer to section 7.3).
Содержание OPC-PRT
Страница 18: ...17 Figure 5 Installation for 15 kW and Smaller Inverters Interface Card Connector Board Option Case...
Страница 19: ...18 Figure 6 Installation for 18 5 kW to 22 kW Inverters Interface Card Connector Board Option Case...
Страница 86: ...85 Figure 85 Monitoring the Data Being Read from the Inverter...
Страница 116: ...47520 Westinghouse Dr Fremont CA 94539 Tel 510 440 1060 Fax 510 440 1063 http www americas fujielectric com...