[Setting example] Setting zero adju1
°
C
Press and hold the
SEL
key for 5 seconds.
will be displayed in the PV display section.
Press the
key to display
.
Press the
SEL
key once.
The current set value ( ) in the SV section flickers.
Press the
and
keys to display .
Press the
SEL
key once. Flickering stops and
=
1
°
C is registered.
The operation is then performed at zero adjustment
+
1
°
C.
To display the operation status, press and hold the
SEL
key for 2 seconds.
Operating procedure
Display
1.
2.
3.
4.
5.
6.
Remote SV input (0%) adjustment (Setting range: -50 to 50% FS) (Option)
Remote SV input (100%) adjustment (Setting range: -50 to 50% FS)
[Description]
* These parameters are used to correct the deviation of remote SV input.
By setting 0 to the parameters, the status at the time of delivery from the factory can be restored.
1. To correct the deviation from zero point (0% input side)
(1) Enter the value equivalent to 0% to remote SV.
(2) Check that
is displayed, and then check the deviation of SV value on the 0% side.
(3) Enter in
the value to correct the deviation observed in (2).
(4) Check on the
display that the input has been corrected.
2. To correct the deviation of span point (on 100% input side)
(1) Enter the value equivalent to 100% to remote SV.
(2) Check that
is displayed, and then check the deviation of SV value on the 100% side.
(3) Enter in
the value to correct the deviation observed in (2).
(4) Check on the
display that the input has been corrected.
Related parameters:
(page 17)
(page 76)
(page 77)