PARAMETER SETTING PRIOR DELEVERY
The damping value (time constant), function of zero/span adjust screw, output current mode,
indicator scale, cut point, mode below cut point and burnout, have been set prior to delivery as
shown in the following.
Each parameter is changed by using FXW (HHC).
N°
Item
contents of parameter
1
Damping value
No damping
(time constant)
(= measuring period)
2
Zero adjust
Zero point adjustable possible
external screw
(Note 1)
3
Current output mode
Could be set in factory
when ordering (note 2)
Digital indicator scale
Could be set in factory
(9th digit of code symbol)
when ordering
4
Cut point
7.07%
(square root extraction mode setting)
5
Mode below cut point
linear
(square root setting)
6
Burnout
Could be set in factory
when ordering (note 3)
7
Lineariz function
Invalid
Note 1) For span adjustment, HHC should be used and can also be used for zero adjustment.
Note 2) In both the differential pressure transmitter (Type: FKC) and remote seal type (Type: FKD), the output
current mode is set in linear unless it is designated.
Note 3) Burnout direction is selectable from HHC, Hold, Over Scale (20.8 to 22.5mA), Under Scale (3.2 to
3.8mA).