51
INSTALLATION AND WIRING
6.1 Installation
During the unpacking of the transmitter, check the conformity of the transmitter and all the ac-
cessories.Before installation, the customer must check the compatibility of the wetted parts for
the application. The possibility of a modi
fi
cation of the process has to be taken in account by
the customer.
The transmitter can be installed on a 2” tube or wall mounted.
The level transmitter FKE has a remote seal and can be installed directly on a counter
fl
ange.
Note :
For the wall mounting, the customer has to supply the M8 bolting. Please refer to the data
sheets for the outline dimension drawings of the transmitters.
An explosion proof certi
fi
ed transmitter has to be used on a process with
explosive gas otherwise there will be a risk of accident (explosion,
fi
re etc)
DANGER
If the transmitter is not used soon after delivery, then leave it packed and store it
in a room at the normal temperature and humidity (25°C <77°F>, 60% RH).
Type
Ambient
Process
Span
Static
Technical
temperature
temperature
limit
pressure
datasheets
limit
limit
limit
Differential
-40 to 85°C
-40 to 120°C
10 mbar
-1 to 32 bar
pressure
60 mbar
-1 to 100 bar
320 mbar
-1 to 160 bar
(option : 420 bar)
EDSF6-114
1300 mbar
-1 to 160 bar
(option : 420 bar)
5000 mbar
-1 to 160 bar
(option : 420bar)
30000 mbar
-1 to 160 bar
(option : 300 bar)
Gauge
-40 to 85°C
-40 to 120°C
1,3 bar
1,3 bar
Pressure
5 bar
5 bar
30 bar
30 bar
EDSF5-80
100 bar
100 bar
500 bar
500 bar
Absolute
-40 to 85°C
-40 to 120°C
0,64 bar abs
0,64 bar abs
Pressure
1,3 bar abs
1,3 bar abs
EDSF5-79
5 bar abs
5 bar abs
30 bar abs
30 bar abs
Level and
-40 to 85°C
-40 to 150°C
320 mbar
According PN/lbs
EDSF6-03
remote seal(s)
(max 400°C
1300 mbar
of remote seal
EDSF7-60
option)
5000
mbar
see note*
30000 mbar
INDICATION
*
Refer to "technical datasheets" about details of process temperature limits of the transmitters.
For speci
fi
c transmitters with static pressure > 420 bar, ask Fuji Electric.
Protect the transmitter with a security device when the existing application
conditions require it. The transmitter should be installed remote from the
measuring point in the case that the process temperature is too high.
INDICATION