34
Saturation current value and specification
Saturation current value (Lower limit
value=SAT LO, Upper limit value=SATO
HI) and speci
fi
cation (NORMAL= Existing
speci
fi
cation, EXP. = Extended speci
fi
ca-
tion) are settable.
When the setting of speci
fi
cation (SPEC) is
for existing speci
fi
cation, saturation current
is not be settable.
When change the setting of saturation cur-
rent, EXP. should be set for the SPEC set-
ting.
• Change of saturation current value (Lower
limit) (Changeable only for the extended
speci
fi
cation) Settable setting range by
<INC> or <DEC> key on the display 3 is
as follows.
3.2mA
≤
Burnout current (UNDER SCALE)
≤
Saturation current (Lower limit value)
≤
4.0mA
• Change of saturation current value (Upper
limit value)
Make a setting as same as the setting of the
lower limit value by input 2 from Menu.
Selectable setting range by <INC> or
<DEC> key is as follows.
20.0mA
≤
Saturation current (Upper limit
value)
≤
Burnout current (OVER SCALE)
21.6mA
* Burnout current is settable according to "9.
Burnout direction and value".
• Change of the speci
fi
cation
Existing speci
fi
cation or enhanced
speci
fi
cation is selectable.
Refer to "J-3" in "J. Saturation current value
and speci
fi
cation" of a local con
fi
gurator
unit with LCD display for details.
1
CL
J:
SATURATE CUR
< 1 >SAT LO Y.YmA
< 2 >SAT HI YY.YmA
< 3 >SPEC XXXXXX
2
ENT
SATURATE LO
2 SATURATE HI
3 SPEC
1
J-1:
SATURATE CUR
SATURATE LO
Y.YmA
J-2:
SATURAT CHNG
SATURATE LO
Y.YmA
3
J-2:
SATURAT CHNG
SATURATE LO
Y.YmA
CHNG OK?< ENT/CL >
4
INC
INC
< CHANGE > < CL >
SATURATE LO
(Lower limit value of
saturation current)
Press <INC> or <DEC> to change
the saturation current value.
(See above)
< INC > < ENT> < CL >
DEC
INC
Y.YmA
4.0mA
3.9mA
3.7mA
3.8mA
3.6mA
3.5mA
3.4mA
3.3mA
3.2mA
CL
1
CHNG
CL
CL
J:
SATURATE CUR
< 1 >SAT LO Y.YmA
< 2 >SAT HI YY.YmA
< 3 >SPEC XXXXXX
5
ENT
1
J-1:
SATURATE CUR
SELECT SPEC
XXXXXX
J-1:
SATURATE CUR
SELECT SPEC
XXXXXX
CHNG OK?< ENT/CL>
6
INC
INC
SPEC
XXXXXX part
:
NORMAL=Standard spec.
EXP.=Extended spec.
DEC
INC
NORMAL
EXP.
CL
3
Menu No.K
< INC> < ENT> < CL>