27
Self-diagnosis
Use for displaying the measured temperature
in the transmitter and the alarm information.
When pressing <1> on display 2 , the tem-
perature in the amplifier (AMP TEMP) is
displayed. When pressing <2>, result of self-
diagnosis about transmitter (ALM CHECK) is
displayed.
Result of diagnosis
When the temperature in the ampli
fi
er is normal:
When temperature alarm is detected:
When no error has occurred:
When an error has occurred:
For contents of error, refer to "Contents of message" on
the next page.
Indication of measured data
The measured value can be indicated.
For more information about operating proce-
dure, refer to the instruction manual of FXW.
C-1:
DATA
STANDBY
PUSH CL KEY
XXX. X %FLOW
C:
DATA
< INC > < ENT >
XXXXX kPa
< CHANGE > < CL >
CL
CL
D-1:
SELF CHECK
D-2:
SELF CHECK
ALM CHECK
< 1 > AMP TEMP
D:
SELF CHECK
< INC > < ENT >
< 2 > ALM CHECK
< 1 > < 2 > <CL >
< CL >
GOOD
D-2:
SELF CHECK
TEMP=XXX.X
o
C
(YYY.Y
o
F)
< CL > <INC>
D-2:
SELF CHECK
CELL FAULT (C1)
< CL > < INC >
D-2:
SELF CHECK
TEMP=XXX.X
o
C
TEMP.ALARM
Temperature is displayed in
o
C and
o
F
alternately at each press of the <INC> key.
1
CL
1
2
2
CL
CL
3
4
5
6
B
DATA
C-1: DATA
XXX. XX %FLOW
XXXXX kPa
< CHANGE > < CL >
CL
:
"FLOW" is displayed
when output mode is
square root extraction
mode.
:
" flicker" is displayed
when the communica-
tion between transmitter
and HHC is normal.
(HHC is not used for 10 minutes)
CHNG
INC
CHNG
ENT
INC
ENT
(Temperature alarm is displayed)
INC
CL
(Trouble in transmitter)
E:
D-2: SELF
CHECK
TEMP=
×××.×
˚
C
<CL>
D-2: SELF
CHECK
CELL FAULT (C1)
<CL> <INC>
D-2: SELF
CHECK
ALM
CHECK
GOOD
<CL>
D-2: SELF
CHECK
TEMP=
×××.×
˚
C
TEMP.
ALARM
<CL>
[Contents of message]
As a result of self-diagnosis, the message below is appeared on the LCD display of HHC, when there are
trouble in the transmitter. For each error, its cause and remedy are suggested.
Indication on digital indicator
CELL FAULT (C1)
CELL FAULT (C9)
(*1)
EEPROM (AMP) FLT
EEPROM (CELL) FLT
TEMP. ALARM
XMTR FAULT
Error of detecting unit
EEPROM error on amplifier side
EEPROM error on cell side
Transmitter temperature is not within the allowable
range (–45 to 90°C).
Amplifier error
Input pressure is 105% or higher of setting range.
Input pressure is –1.25% or lower of setting range.
Replacement of detecting unit
Replacement of amplifier
Replacement of detecting unit
Transmitter temperature is normalized.
Replacement of amplifier
Properly controlled.
Properly controlled.
Message
Remedy
Cause
FL-1
FL-2
FL-3
T.ALM
FL-1
OVER
Under
ZERO
ZERO
ZERO
(*2)
(*2)
(*2)
(*1) CELL FALUT (C5) to (C9) are appeared in case of “9” in 6th digit code of FKC.
(*2) Real indication