24
Used for selecting output at occur-
rence of a fault in the detecting unit.
Burnout direction is selectable under
display 2
• For selection of NOT USED, press
<1>.
• For selection of OVER SCALE,
press <2>.
• For selection of UNDER SCALE,
press <3>.
The meaning of each condition
above is as follows.
• NOT USED
Not used
(Output hold)
Saturation current = 3.8, 20.8mA
Note)
Output value just before the occur-
rence of trouble is given in the output
hold mode.
• OVER SCALE
Over scale
(Output 20.8 to 21.6mA)
Saturation current = 3.8, 20.8mA
• UNDER SCALE Under scale
(Output 3.2 to 3.8 mA)
Saturation current = 3.8, 20.8mA
Burnout Current of FCX-AII series
transmitter
Over scale burnout current = 20.8 to
21.6mA
Under scale burnout current=3.2 to
3.8mA
Saturation current = 3.8, 20.8mA
Burnout direction
CHNG
3
9-2:
BURNOUT
CHANGE
CHNG OK? < ENT/CL >
4
5
6
2
9:BURNOUT
NOT USED
(HOLD)
< INC > < CHANGE >
1
9-2:
BURNOUT
CHANGE
Selection of
burnout direction
(ex)
< ENT > < CL >
CL
CL
CL
CHNG
CHNG
ENT
INC
CL
CL
or
or
2
1
3
3
9-1:
BURNOUT
< 1 > NOT USED
< 2 > OVER SCALE
< 3 > UNDER SCALE
UNDER SCALE
9-4:
BURNOUT
< CHANGE > < CL >
UNDER SCALE
Y.YmA
9-5: BURNOUT
< CL >
Saturate Current
3.8-20.8mA
9-5:
BURNOUT CHNG
< DEC > <ENT > < CL >
UNDER SCALE
UNDER SCALE (burnout current)
Y.YmA
UNDER SCALE
ENT
ENT
ENT
INC
7
8
9
10
CL
CL
9-5:
BURNOUT CHNG
CHNG OK? < ENT/CL >
UNDER SCALE
Y.YmA
9: BURNOUT
< INC > < CHANGE >
UNDER SCALE
Y.YmA
Upon pressing <DEC> or <INC>
burnout current can be changed.
(See above.)
9-7:
BURNOUT
< CL >
Saturate Current
3.8-20.8mA
INC
DEC
Y.YmA
3.8mA
3.7mA
3.6mA
3.5mA
3.4mA
3.3mA
3.2mA
A : CALIBRATE
A : CALIBRATE
Change of Over scale current
21.6mA
21.5mA
21.4mA
21.3mA
21.2mA
21.1mA
21.0mA
20.9mA
20.8mA
INC
DEC