Pulsers
The wiring configuration for pulsers depends on
whether you are using a 2-wire (passive) or a 3-wire
(active) pulser. All pulser wiring should be connected
to the bank of terminals on the left on the bottom
of the FuelCloud board, as demonstrated in the
graphic on the right.
Note: for 2 wire pulsers, it doesn’t matter which of
the two wires you attach to each terminal.
Note: 3 wire pulser if pulser requires 12V DC power.
• Attach one wire to the terminal marked ‘Pulse’.
• Attach one wire to the terminal marked ‘GND’.
• Attach the pulser 12V power wire to the ‘12V+’
terminal.
• Attach signal wire to the ‘Pulse’.
• Attach the ground wire to the GND terminal.
2-Wire (Passive) Pulser:
3-Wire (Active) Pulser:
Warning:
Do not attach AC power to the terminal marked
“12V+”. This terminal is for DC active pulsers only. Attaching
AC power to this terminal will destroy your FuelCloud
board.