DigiTemp User Manual 

Chapter 2  SDI Commands 

 

page 9 

2.1

 

Notation for SDI commands 

In the end, SDI commands are strings of characters sent to the SDI device. The format of those strings is 
important, of course, and to specify the format of SDI commands we use different typefaces. All commands 
(and the replies from the device) are represented in a monospaced font, 

thus

. Different parts of a command 

are represented with variants on this text format. 

Item 

Meaning 

Text representation 

Command literal 

Part of a command that must be 

reproduced literally as it appears; 

Command 

parameter 

Part of a command that must be filled in 

with an appropriate value 

data 

2.2

 

Commands recognized by DigiTemp 

The table below provides a quick reference to the commands recognized by the DigiTemp. For details on these 
commands, see the following sections. 

Command name 

Command code 

Notes 

Address Query 

?! 

 

Acknowledge Active 

a

 

Change Address 

a

A

b

 

Send Identification 

a

I! 

 

Start Measurement 

a

M!

a

MC!

 

C

 following a command requests a CRC code 

in the data return (

D

 command) 

Start Concurrent Measurement 

a

C!

a

CC!

 

C

 following a command requests a CRC code 

in the data return (

D

 command) 

Send Data 

a

D

b

 

Continuous Measurements (Read) 

a

R!

a

RC!

 

C

 following a command requests a CRC code 

in the data return 

Start Verification 

a

V! 

 

2.3

 

General SDI commands 

General SDI commands are used for housekeeping issues such as device address configuration, device 
identification and confirmation of device communications. General SDI-12 version 1.3 commands are as 
follows. 

Содержание DigiTemp

Страница 1: ...1 800 548 4264 www ftshydrology com 700 DigiTemp Rev 1 0 24 Nov 2011 DigiTemp SDI 12 Submersible Digital Temperature Sensor User Manual...

Страница 2: ...Contact information FTS 1065 Henry Eng Place Victoria B C V9B 6B2 CANADA www ftshydrology com Toll free 1 800 548 4264 Local 250 478 5561 Technical support support ftshydrology com...

Страница 3: ...Revision History Date Person Description 24 Nov 2011 RG First released version 28 Nov 2011 RG Late corrections...

Страница 4: ...3 Connection 7 1 4 Operation 7 1 5 Configuration 7 1 6 Calibration and maintenance 7 Chapter 2 SDI Commands 8 2 1 Notation for SDI commands 9 2 2 Commands recognized by DigiTemp 9 2 3 General SDI com...

Страница 5: ...Chapter 1 Operation Chapter contents 1 1 General description 6 1 2 Installation 6 1 3 Connection 7 1 4 Operation 7 1 5 Configuration 7 1 6 Calibration and maintenance 7...

Страница 6: ...these steps 1 Place the sensor in a location where it is continuously immersed in a representative sample of the water to be monitored usually a well mixed locale 2 The sensor may be mounted on an ob...

Страница 7: ...s powered by the 12 V DC power supply on the SDI 12 bus For details on the SDI commands used by the sensor see Chapter 2 SDI Commands 1 5 Configuration The DigiTemp is shipped with default address 0 u...

Страница 8: ...2 3 General SDI commands 9 2 3 1 Address Query 2 3 2 Acknowledge Active 2 3 3 Change Address 2 3 4 Send Identification 2 4 SDI Data commands 10 2 4 1 Start Measurement 2 4 2 Start Concurrent Measureme...

Страница 9: ...Commands recognized by DigiTemp The table below provides a quick reference to the commands recognized by the DigiTemp For details on these commands see the following sections Command name Command code...

Страница 10: ...address String Note Cmd 0 request the device at address 0 to confirm it is active Resp 0 a device is present at address 0 2 3 3 Change Address This command changes a sensor s SDI address String Note C...

Страница 11: ...Table 2 String Note Cmd 3C or 3CC start a concurrent measurement on sensor at address 3 without or with CRC in data response respectively Resp 300302 3 device SDI address 003 measurement delay until d...

Страница 12: ...ata is returned Cmd 1RC perform a continuous measurement read on sensor at address 3 with CRC code in data response Resp 1MSA 1 sensor SDI address MSA CRC code DigiTemp is not a continuous measurement...

Страница 13: ...Chapter 3 Technical specifications...

Страница 14: ...may be less accurate Responsiveness Time constant 0 57 min reaches 95 of final value in 1 7 min 99 in 2 9min Measurement time 3 s Power supply voltage 12 V DC nominal range 9 6 V 18 6 V Standby curre...

Отзывы: