PROBLEM

 

POSSIBLE CAUSE 

 

POSSIBLE SOLUTION

 

The heater does 

not start or does 

not operate

 

1.

 

Starter switch in “OFF” (0)      

position

 

2.

 

No power supply

 

 
 

3.     Power supply cable interrupted 

 

4.     Electronic control board blocked             

or malfunctioning

 

5.

 

Incorrect setting of the room 

thermostat (if present)

 

6.

 

No fuel

 

7.

 

External substances or dirt in the 

fuel circuit

 

1. Set starter switch to “ON” (I) position (pic 1)

 

2a. Insert the power plug into the mains socket correctly (pic 2)

 

2b. Check voltage of your electric supply system

 

2c. In duel voltage models (..DV) (pic 3) set the switch to the correct    

voltage position required.

 

3. Contact a service center

 

4a. Reset the heater (SEE PAR. 7.2.)

 

4b. Contact a service center

 

5. Set the room thermostat to a temperature higher than the working   

environment temperature (pic 4)

 

6. Top off fuel and reset heater

 

7a. Empty, rinse and refill the tank

 

7b. Rinse the filters (SEE PAR. 8.)

 

7c. Contact a service center

 

Smoke while 

operating

 

1.

 

External substances or dirt in the 

fuel circuit

 

2.

 

Obstructed inlet air vent

 

1a. Empty and refill the tank with clean fuel

 

1b. Rinse fuel filters

 

1c. Contact a service center

 

2. Remove all air vent obstructions

 

The heater does 

not turn off

 

1. Faulty electronic system 

 

1. Contact a service center

 

COMPONENT

 

MAINTENANCE FREQUENCY 

 

MAINTENANCE PROCEDURE

 

Fuel tank

 

Clean once a year or as required

 

Empty and rinse the tank with clean fuel (SEE PAR. 9.)

 

Filters

 

Clean or replace once a year or as required 

(make sure they are intact)

 

Clean the filters (SEE PAR. 8.)

 

Fuel pump filter

 

Clean or replace once a year or as required 

(make sure they are intact)

 

Contact a service center

 

Electrodes

 

Clean as required

 

Contact a service center

 

Fan

 

Clean as required

 

Contact a service center

 

Combustion chamber

 

Clean as required 

 

Contact a service center

 

11. PREVENTIVE MAINTENANCE SCHEDULE

 

12. TROUBLESHOOTING

 

(1)

 

(2)

 

(3)

 

(4)

 

Содержание F-HVF1101

Страница 1: ... Lake Ohio 44054 Phone 440 949 2400 Fax 440 949 2900 Email sales fsinorth com Visit us on the web at www fsinorth com 03 16 PORTABLE AIR HEATERS MANUAL FSI OIL INDIRECT FIRED AIR HEATER MODELS F HVF1101 F HVF2101 F HVF3101 ...

Страница 2: ...N MONOXIDE A CHEMICAL KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER AND BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARNING NOT FOR HOME OR RECREATIONAL VEHICLE USE We cannot anticipate every use which may be made for our heaters CHECK WITH YOUR LOCAL FIRE SAFETY AUTHORITY IF YOU HAVE QUESTIONS ABOUT LOCAL REGULATIONS Other standards govern the use of fuel gases and heat producing products in spec...

Страница 3: ... FUEL OIL 17 GAL 17 GAL 27 7 GAL 120 V 15 10 60 HZ 7 5 A 0 9 KW 120 V 15 10 60 HZ 7 5 A 0 9 KW 120 V 15 10 60 HZ 11 4 A 1 4 KW 135 LB 148 LB 271 LB NOZZLE 0 65 US GPH 80 S DANFOSS 1 00 US GPH 80 S DANFOSS 1 50 GPH 80 S DANFOSS PRESSURE 174 PSI 12300 KPA 12 BAR 145 PSI 1000KPA 10 BAR 174 PSI 1200KPA 12 BAR CERT TECHNICAL DATA IMPORTANT In order to have a correct function you must use an electrical ...

Страница 4: ... criteria The safety devices ensure the machine always operates correctly IMPORTANT This appliance is not suitable for use by persons including children with reduced physical sensory and mental capacities or with lack of experience or knowledge unless supervised by a person responsible for their safety Children must be supervised to make sure they do not play with the appliance DANGER Suffocation ...

Страница 5: ...5v supply must be available Please note that the heater requires minimum 15 amps for proper operation Ensure appropriate gauge extension cord is used 12 3 AWG at 50 Ft 10 3 AWG at 100 Ft 2 2 7 The recommended safety distances between heaters and flammable substances are front output 5 ft side top output 2 ft 2 2 8 Avoid fire hazards by placing the hot or functioning heater on a flat level surface ...

Страница 6: ...et button turns on with a steady red light pic 5 it means the heater needs to be reset To reset the heater press the reset button all the way down pic 6 Identify and remove the cause that stopped the appliance for instance obstruction of air intake and or outlet total block of the fan etc Please contact an appointed service center for assistance in case it is impossible to solve the problem 7 3 SW...

Страница 7: ...8 4 FUEL PUMP FILTER See the preventive maintenance schedule 9 STORAGE AND TRANSPORT IN ORDER TO KEEP THE HEATER IN THE BEST POSSIBLE CONDITIONS WE RECOMMEND TO FOLLOW THE BELOW PROCEDURE 9 1 Empty the fuel by removing the drain cap at the bottom of the tank pic 5 Dispose of the fuel in an appropriate container in accordance with the current safety regulations 9 2 To remove any residual remaining ...

Страница 8: ...he working environment temperature pic 4 6 Top off fuel and reset heater 7a Empty rinse and refill the tank 7b Rinse the filters SEE PAR 8 7c Contact a service center Smoke while operating 1 External substances or dirt in the fuel circuit 2 Obstructed inlet air vent 1a Empty and refill the tank with clean fuel 1b Rinse fuel filters 1c Contact a service center 2 Remove all air vent obstructions The...

Отзывы: