FSA GT1-12LS Скачать руководство пользователя страница 4

have higher incoming salt rather than higher hardness. For this reason, a water softener is installed behind 
an RO System. 

Due to the flow rates of a water softener, it will generally need to be installed in the following order: Feed 
Supply 

 Softener 

 Holding Tank 

 Pump 

RO System 

 Use or further filtration. 

Aeration/Filtration: 

Given the correct water chemistry, levels or iron/manganese may be the only issue in 

the water. This method is designed to remove these metals from the water without affecting the other 
minerals in the water and without increasing the salt levels. The aeration/filtration will be set up in the same 
configuration as the water softener. 

Calcite Filter:

 Reverse Osmosis will strip the minerals and salts from the water. The trade off is that the 

water will then usually become ‘aggressive’ much like rain water. The pH will be low and the LSI of the 
water will be low. 

To use this water safely in a domestic setting, the pH and LSI will need to be balanced by using a Calcite 
Filter. This will dissolve small amounts of calcium into the water to balance the pH and LSI. The most 
common use of a calcite filter is in the following orientation: RO System 

 Tank 

 Calcite Filter 

 

Standard Filtration (Big Blue) 

 UV 

 House 

De-Ionising (Demineralising):

 DI units are common as they are now required for medical sterilisation. DI 

systems or housings are installed in the following configuration; RO System 

 Tank (If Applicable) 

 DI 

Filter 

 Direct Point of use. 

Installation Introduction 

I. Site Preparation 

When a suitable installation location is identified, you will need to determine if the system will be mounted 
to a wall or free-standing. The System should ideally have both the water supply (feed water) & 
Storage/Point of use within a 5m radius of the system to reduce negative effects on the pressure/flow and 
performance of the system. It is also recommended that the process water (filtered water) does not have to 
travel more than 2m elevation above the system. This will ensure that minimal backpressure is applied to 
the pumps. Where possible, have the water running to a point lower than or at the level of the system for 
best results. 

Ensure that adequate space is allowed for to access all parts of the system and if mounted to a wall, the 
fixings should be removable which can help maintenance. 

II. Installation – Mounting 

When mounting the system, you will need to position the system to the desired location and mark out the 
mounting holes. NOTE: it can help to unscrew and remove the blue cannisters on the front of the unit to 
reduce weight and gain better access to the mounting points to mark them. 

III. Installation – Free-Standing 

The frame of the unit is suitable to support the system if it is not mounted to a wall. You will need a firm 
stable base such as concrete for the system to sit on. Where possible, it is best to fix the system to the 
ground or adjacent structure that is already secured. This is to prevent the system tipping over and also to 
prevent the system putting pressure on any of the plumbing connections. 

IV. Installing Connections – Quick Connect 

If you come across a push-fit fitting, you need to firmly push the tubing into the 
opening until you feel a “click” which signifies that the tubing has pushed 
through the internal O-ring and is seated correctly. If leaking occurs, it may be 
due to roughly cut tubing OR the tubing is not pushed in far enough. To 
remove tubing from push-fit fittings, depress the floating collet (shown to the 
right), then pull the tubing out. The LSRO units are fitted with Blue locking clips. 
These will need to be removed first so you can release the fitting. You will also 
need to remove them from the fitting if you are trying to re-install the tubing. 

 

Содержание GT1-12LS

Страница 1: ...ion Introduction 4 I Site Preparation 4 II Installation Mounting 4 III Installation Free Standing 4 IV Installing Connections Quick Connect 4 V Filter Protection 5 VI Drain Waste 5 VII Cartridge Insta...

Страница 2: ...ed below If these conditions are not met the system may not be suitable for the application and may not function as specified These systems are designed for filtration on mains water for the removal o...

Страница 3: ...s which may require treating before the system Bore Water filtration is used when the water meets specific conditions where an RO unit will be suitable to remove elevated salt levels in the water gene...

Страница 4: ...tem to reduce negative effects on the pressure flow and performance of the system It is also recommended that the process water filtered water does not have to travel more than 2m elevation above the...

Страница 5: ...ted Before Spun Spun Before Carbon Highest Micron Before Lowest Micron As an example a common filter set would be 5uM Polyspun 20uM Low Pressure Carbon 0 5uM Chloramine Reduction Carbon You would inst...

Страница 6: ...straight cut with no rough edges Measure a length of tubing from the drain valve located behind the pumps which is marked as to drain or Flow 2000 to a suitable drainage point Measure a length of tubi...

Страница 7: ...s the filters are classed as a consumable item III Automation The system is fitted with high and low pressure switches This will allow the system to know when to shut off due to the tank being full or...

Страница 8: ...arbon Block 6 12 Months RO Membranes GT13 37 ALP Asprinn Reverse Osmosis Membrane 100GPD TDS Checking Required 4 pc Required 1 3 Years Post Filters GT6 7C 5 Micron inline GAC 2 5 5 000L 6 Months GT6 2...

Страница 9: ...ing pH levels in lower EC water i e The guy at the pool shop is not going to cut it We have access to high quality testing equipment and frequently test our units and conduct research If you feel that...

Страница 10: ...pump may require replacing if it has been overworked outside the manufacturer s guidelines 2 Power surges may cause the power supply to short out Other things include water leaking or overheating An...

Страница 11: ...of of installation in the form of an invoice and or receipt Filter systems must be maintained as per FSA recommendations including the use of replacement filters fittings and components supplied by FS...

Страница 12: ...f the system is installed on an open circuit a plumber may not be required in this case the system must be installed in accordance with the user manual and determined to be correctly installed by FSA...

Отзывы: