Energy
Reactive energy accuracy
(EN IEC 62053-23)
Class 2
Response time after switch-on
(EN IEC 62053-21, EN IEC 62053-23)
< 5 s
kCT x kVT
Maximum display
Resolution
1 - 9.9
9 9 9 9 9 9 . 9 9 kWh / kvarh
10 Wh / varh
10 - 99.9
9 9 9 9 9 9 9 . 9 kWh / kvarh
100 Wh /
varh
100 - 999.9
9 9 9 9 9 9 9 9 kWh / kvarh
1 kWh / varh
≥ 1000
9 9 9 9 9 9 . 9 9 MWh / kvarh
10 kWh /
varh
Average power
Measured variable
Effective power
Calculation
Average value over set period of time
Integration time
5 / 8 / 10 / 15 / 20 / 30 / 60 minutes
Output
RS485 communication
Electrically isolated from input and auxiliary voltage
Standard
RS485 - 3 conductors
Transmission
Serial, asynchronous
Protocol
Modbus RTU
Addresses
1 - 255
Number of bits
8
Stop bit
1
Parity bit
None - even - odd
Baud rate
9600, 19200, 38400 bit/s
Response time
≤ 200 ms
Insulation (EN IEC 62052-11, EN IEC 62053-21)
Installation category
III
Pollution degree
2
Insulation voltage
4 kV RMS
Impulse withstand voltage
Test circuit
4 kV 1.2/60
µ
s
Voltage input, current input, pulse
output, communication
Test voltage
Test circuit
2.75 kV RMS. 50 Hz/1 min
Voltage input, current input, pulse
output, communication
Test voltage
Test circuit
4 kV RMS. 50 Hz/1 min
All circuits and earth
45
EN
Содержание TS 5kA-3
Страница 2: ......
Страница 4: ...Fronius manufacturer s warranty 46 4...
Страница 5: ...Safety rules 5...
Страница 6: ...6...
Страница 9: ...General information 9...
Страница 10: ...10...
Страница 15: ...Installation 15...
Страница 16: ...16...
Страница 37: ...Start up 37...
Страница 38: ...38...
Страница 43: ...The Fronius Smart Meter TS is configured as a secondary meter 43 EN...
Страница 47: ...47 EN...
Страница 48: ......