Image
Scree
n
Description
16
1
.
Phase voltage
18
1
.
Operating hours counter
2
.
Neutral current
19
1
.
Current
20
1
.
Effective power
*
Displayed when easy connection mode is activated (
measurement
= A).
This value indicates the total energy without considering the direction.
**
Factory setting - displayed when drawn and delivered energy are meas-
ured separately (
measurement
= b).
Configuration
menu - structure
and parameters
Screen
Code
Description
Values
PASS***
P1
Enter the current password
2633*
nPASS
P2
Password change **
Four digits (0000-9999)
SYStEM
P3
Type of system
3Pn*: three-phase system,
4-core
3P: three-phase system, 3-
core
2P: two-phase system, 3-
core
Ct rAtIo
P4
Current transformer ratio
from 1* to 1000
Ut rAtIo
P5
Voltage transformer ratio
from 1* to 1000
MEASurE
P6
Measurement mode **
A: easy connection, meas-
ures all energy without tak-
ing the direction into ac-
count.
B*: measures imported and
exported energy separately.