
Energy saving mode
General
Energy saving mode (standby mode) is used to reduce the self-consumption of the sys-
tem. Both the inverter and the battery automatically switch into energy saving mode
under certain conditions.
The inverter switches into energy saving mode if the battery is flat and no PV power is
available. Only the inverter's communication with the Fronius Smart Meter and Fronius
Solar.web is maintained.
Switch-off condi-
tions
If all the switch-off conditions are met, the battery switches into energy saving mode
within six minutes. This time delay ensures that the inverter can at least be restarted.
< min. SoC
The battery state of charge is less than or equal to the input min-
imum state of charge.
< 50 W
The power from the solar modules is less than 50 W.
< 100 W
The current charging or discharging power of the battery is less
than 100 W.
< 50 W
Less than 50 W is available for charging the battery. The power of
feeding into the public grid is at least 50 W less than the power cur-
rently required in the home network.
The inverter automatically switches into energy saving mode, following the battery.
Switch-on condi-
tions
If one of the following conditions is met for at least 30 seconds, energy saving mode is
ended:
-
Energy saving mode is no longer permissible owing to a changed setting on the
website of the inverter.
-
More than 50 W is available for charging the battery. The power of feeding into the
public grid is at least 50 W greater than the power currently required in the home
network.
-
If dynamic power reduction of 0 is set, or if the system is operating in backup power
mode, the power of feeding into the public grid is always less than the required
power in the home network.
There is a separate condition for this case (dynamic power reduction < 300 W or
active backup power mode): If the PV power is above a specified threshold (50 W),
the energy saving mode is ended.
-
Battery charging from the public grid is requested via the website.
-
The battery is being recharged in order to restore the minimum state of charge or
perform calibration.
Special case
If the inverter does not operate for 8–12 minutes (e.g.: error), or if there is an interruption
in the electrical connection between the inverter and battery, the battery switches into
energy saving mode in any case. This reduces self discharge of the battery.
19
EN
Содержание Symo GEN24 10.0
Страница 2: ......
Страница 10: ...10 ...
Страница 11: ...General information 11 ...
Страница 12: ...12 ...
Страница 28: ...28 ...
Страница 29: ...Backup power variant PV Point OP 29 ...
Страница 30: ...30 ...
Страница 32: ...32 ...
Страница 33: ...Backup power variant Full Backup 33 ...
Страница 34: ...34 ...
Страница 41: ...Installation 41 ...
Страница 42: ...42 ...
Страница 82: ...82 ...
Страница 83: ...Settings web interface of the inverter 83 ...
Страница 84: ...84 ...
Страница 104: ...104 ...
Страница 105: ...Appendix 105 ...
Страница 106: ...106 ...
Страница 116: ...116 ...
Страница 117: ...Circuit diagrams 117 ...