Visual inspections
General
The following must be visually inspected without any further dismantling of the device.
Obvious defects in any safety-related device components are unacceptable. Defects that
could pose a risk during the visual inspection must also be recorded.
Any defects that could cause other hazards must be repaired immediately or restrictions
placed on the further use of the system until repairs have been effected.
Mains supply and
connecting lines
-
Connecting lines and other cables must not be damaged or defective
-
Insulation must not be damaged (do not use insulating or adhesive tapes to repair
damage)
-
Connectors and plug connections must not be damaged or deformed
-
Strain-relief devices, bending-protection devices, line routings or mountings must all
be effective
-
Lines/plugs must be suitable for the application and the power level
-
Fuse cartridges and device fuse holders must not be faulty
ATTENTION! ?
IEC 60364-5-52 serves as the basis for determining the cross-section and current
capacity of mains cables.
As the way the cables are laid and insulated, the ambient temperature and the current
capacity can vary, the requirements set out in IEC 60364-5-52 are to be observed when
changing mains leads. Also refer to the applicable requirements and standards in your
country.
Housing and cov-
ers
-
All housing components, insulation components and protective covers must be
present and undamaged
-
Unauthorised modifications may not have been made, e.g.: Installations or conver-
sions that have not been approved by the manufacturer
-
Cooling openings must not be dirty or blocked and an air filter must be present
-
Any dirt, corrosion or degradation that impairs safety must not be visible
-
There must be no signs of overloading or improper use
-
There must not be any conductive objects in the housing
Adjustment and
display devices
-
Control elements and indicators must not be faulty
Rating plate and
warning stickers
-
Safety-related labels (e.g. warning notices, earthing symbols, rating plates, etc.)
must be present. Replace, update or correct the labels as required
-
The legibility of all safety-related labels or symbols, measurement data and position-
ing indicators must be ensured
47
EN
Содержание Selectiva 2040
Страница 2: ......
Страница 5: ...General information 5 ...
Страница 6: ...6 ...
Страница 12: ...12 ...
Страница 13: ...Replacing components 13 ...
Страница 14: ...14 ...
Страница 21: ...1 Fit the front panel of the housing see chapter Closing the device 21 EN ...
Страница 27: ...1 2 2 1 Fit the DC connection plate and secure with two 4x20 TX20 screws Tightening torque 1 5 Nm 27 EN ...
Страница 32: ...1 1 Fit the M4x10 TX20 screw on the device frame AC side Tightening torque 2 5 Nm 32 ...
Страница 34: ...1 Fit the housing cover see chapter Closing the 2 kW device 34 ...
Страница 42: ...42 ...
Страница 43: ...Safety Inspections 43 ...
Страница 44: ...44 ...
Страница 59: ...59 EN ...