Installation location and position
Choosing the loc-
ation of the
inverter
Please note the following criteria when choosing a location for the inverter:
Only install on a solid, non-flammable
surface.
Max. ambient temperatures:
-40 °C - +60 °C
-40 °F - +140 °F
Relative humidity:
0-100%
If the inverter is installed in a switch cab-
inet or similar enclosed space, ensure
sufficient heat dissipation with forced-air
ventilation.
For detailed information on the dimen-
sions of the inverter, see chapter
page
When installing the inverter on the outer walls of cattle sheds, it is important to main-
tain a minimum clearance of 2 m between the inverter and the ventilation and building
openings on all sides.
The following surfaces are permissible for installation:
-
Walls (corrugated metal walls [mounting rails], brick walls, concrete walls or other
non-flammable surfaces sufficiently capable of bearing loads)
-
Poles (installed using mounting rails, behind the solar modules directly on the PV
mounting system)
-
Flat roofs (if this is for a film roof, make sure that the films comply with the fire
protection requirements and are not highly flammable. Ensure compliance with
the national provisions.)
-
Covered car park roofs (no overhead installation)
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its IP 66 protection class, the inverter is resistant to water
jets from any direction and can also be used in damp environments.
47
EN
Содержание Primo GEN24 3.0 Plus
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Backup power variant Full Backup 35...
Страница 36: ...36...
Страница 43: ...Installation 43...
Страница 44: ...44...
Страница 50: ...Do not install the inverter on the ceiling 50...
Страница 84: ...84...
Страница 90: ...90...
Страница 91: ...Settings website of the inverter 91...
Страница 92: ...92...
Страница 110: ...I O power man agement settings 4 relays 110...
Страница 112: ...I O power man agement settings 3 relays 112...
Страница 114: ...I O power man agement settings 2 relays 114...
Страница 118: ...118...
Страница 119: ...Options 119...
Страница 120: ...120...
Страница 129: ...Appendix 129...
Страница 130: ...130...
Страница 143: ...Circuit diagrams 143...
Страница 144: ...144...
Страница 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Страница 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Страница 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Страница 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Страница 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Страница 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Страница 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Страница 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Страница 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Страница 155: ...Dimensions of the inverter 155...
Страница 156: ...156...
Страница 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Страница 158: ...158...
Страница 159: ...159 EN...