47
EN
*) If the status code is displayed all the time: notify a Fronius-trained service engineer
**) Fault is rectified automatically. If this status code keeps recurring, contact your system
engineer
Status codes –
Class 4
Some of the class 4 status codes necessitate intervention by a Fronius-trained service
technician.
Code
Description
Behaviour
Remedy
301
Overcurrent (AC)
Short-term interruption while
feeding energy into the grid.
The inverter resumes its start-
up routine.
*)
302
Overcurrent (DC)
303
DC module overtemperature
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
Purge cooling air open
-
ings and heat sink; **)
304
AC module overtemperature
305
No power being fed in, despite closed
relay
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
**)
306
PV output too low for feeding energy
into the grid
Short-term interruption while
feeding energy into the grid
The inverter resumes its start
-
up routine.
wait for sufficient level of
insolation;
**)
307
DC low
DC input voltage too low for feeding
energy into the grid
IMPORTANT!
Due to the low level of insolation early in the morning and in the evening, the status codes 306
(Power low) and 307 (DC low) are displayed routinely at these times of day. These status codes do not indicate
any kind of fault.
308
Intermediate circuit voltage too high
Short-term interruption while
feeding energy into the grid
The inverter resumes its start
-
up routine.
**)
309
DC input voltage MPPT 1 too high
311
Polarity of DC strings reversed
313
DC input voltage MPPT2 too high
314
Current sensor calibration timeout
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
*)
315
AC current sensor error
316
InterruptCheck fail
325
Overtemperature in the connection
area
326
Fan 1 error
327
Fan 2 error
Code
Description
Behaviour
Remedy
401
Unable to communicate with the power
stage set
The inverter will automati
-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid
*)
406
AC module temperature sensor faulty
(L1)
407
AC module temperature sensor faulty
(L2)
408
DC component measured in the grid too
high