2.7 Emergency procedure
2.7.1 Overheating of the system
If the system overheats and the safety devices fail to operate, proceed as follows:
NOTICE! Do not under any circumstances switch off the main switch or disconnect the
power supply!
❒ Keep all the doors on the boiler closed
❒ Open all mixing valve taps, switch on all pumps.
➥ The Froling heating circuit control takes on this function in automatic operation.
❒ If a third-party controller is used, carry out the appropriate measures to activate
the mixer taps and pumps manually.
❒ Leave the boiler room and close the door
❒ Increase heat consumption by turning on all radiators and other appliances
❒ Open any thermostatic valves on the radiator and ensure sufficient heat
dissipation from the rooms
If the temperature does not drop:
❒ Contact the installer or Froling customer services
2.7.2 Smell of flue gas
DANGER
If you smell flue gas in the boiler room:
Inhaling toxic flue gas can be fatal!
If you smell flue gas in the room where the boiler is installed:
❒ Keep all the doors on the boiler closed
❒ Shut down the boiler according to procedure
❒ Ventilate the room where the boiler is installed
❒ Close the fire door and doors to living areas
Recommendation: Do not install smoke alarms and carbon monoxide detectors near
the system.
2.7.3 Fire in the system
DANGER
In case of fire in the system:
Risk of death by fire and poisonous gases
Emergency procedure in case of fire:
❒ Leave the boiler room
❒ Close the doors
❒ Inform the fire department
Safety
2
Emergency procedure
Operating Instructions TI 350 | B1380220_en
21