6 | Assembly
46
M1980822_en | Installation instructions Wood chip boiler T4e 20-180
6.3.3 Control the return temperature control
r
Remove both back panels
r
Tighten all of the connections on the return temperature control using a pipe wrench
Ä
Connections may have loosened during transport.
Ä
IMPORTANT:
Before and after filling the system with heated water, check the seal
of the screw connections on the return temperature control
Return temperature control left
r
Set the knob on the housing of the mixing drive to manual mode (A)
r
Turn the mixing drive counter clockwise until it stops
Ä
The mixer valve completely closes off the system return
r
Turn the mixing drive clockwise until it stops
Ä
The system return is completely open and the bypass line coming from above is
completely closed