5.6.3 Cleaning the Lambda probe
❒ Remove the cover plate on the boiler flow
❒ Press the thermal insulation behind it slightly downwards
❒ Carefully remove the Lambda probe (1) and plastic bushing (2 – if installed)
➥ Pay attention to the cables of the Lambda probe!
❒ Carefully remove impurities from the measuring ports with a fine brush and ash
vacuum
➥ Hold the Lambda probe with the tip downwards so that deposits can fall out of
the measuring ports
❒ Check the plastic bushing (2) for dirt and cracks, replace if necessary
➥ IMPORTANT: The seal surface of the plastic bushing must lie flat after
assembly
CAUTION:
▪ Do not clean the Lambda probe with compressed air
▪ Do not use chemical cleaning agents (brake cleaner, etc.)
▪ Careful handling of the Lambda probe, no “tapping” or cleaning with a wire brush
5
Servicing the system
Maintenance work by technicians