4.5.5 Resetting the pellet consumption counter
The pellet consumption counter indicates the consumption of pellets in the parameters
“
Resettable t-counter
” and “
Resettable kg-counter
” in steps of tons or
kilograms. Both values are set to “0” by resetting.
Examples of use for the counter:
▪ Monthly accounting to illustrate seasonal changes in pellet consumption
▪ Seasonal accounting (e.g. during the winter months) to illustrate annual changes
in pellet consumption
❒ In the “
Consumption
” menu, set the “
RESET counter
” to “
YES
”
➥ Values of the parameters “
Resettable t-counter
” and “
Resettable kg-
counter
” are reset to “0”
➥ Parameter “
RESET counter
” is reset to “
NO
”
4.6 Checking the fill level of the ash container and emptying if required
The ash container must be emptied at appropriate intervals depending on energy
requirements and fuel quality. The grate, burn-out tray and combustion chamber
should also be checked at these intervals.
WARNING
When removing the ash container cover during operation:
False air infiltration via the ash screw duct can lead to uncontrolled combustion
and the risk of accidents.
Before checking the ash level / emptying the ash container:
❒ Switch off the boiler by tapping “Boiler off”
➥ The boiler follows the shutdown procedure and switches to "Boiler off"
status.