Analogue module input for external power demand
Defines the input for the external power demand with a
specified power of “0-10V“ (address of analogue module
and input terminal, e.g. 0.3).
Boiler - General settings - MODBUS settings
System menu
Boiler
MODBUS
settings
COM 2 is used as a MODBUS interface
▪ NO: The COM 2 interface sends the most important
boiler values every second.
▪ YES: The COM 2 interface can be used to connect a
MODBUS (RTU/ASCII).
MODBUS address
Defines the address of the boiler in the Modbus network.
MODBUS protocol (1 – RTU / 2 – ASCII)
Indicates which Modbus protocol is to be used for the
transfer. Which protocol must be used can be found in the
documentation of the Modbus system used on site.
Use MODBUS protocol 2014?
Indicates whether the Modbus protocol 2014 is to be used
for communication. In this version, parameters can be
written at the customer level. In addition to the previous
version, the element addresses are newly grouped
thematically.
If the parameter is set to “NO”, the functionality and the
element addresses remain the same as in the previous
version to ensure compatibility with existing systems in the
event of software updates.
Boiler - General settings - Operator data
System menu
Boiler
Operator data
Production number
For unique identification of the boiler on the froeling-
connect server, the facility number listed on the
identification plate must be set here.
Customer number
By setting the customer number, this is automatically
transferred into the commissioning report when it is saved.
Boiler number
By setting the boiler number, this is automatically
transferred into the commissioning report when it is saved.
4
Parameters overview
Boiler
68