5.3 Filling the store with fuel
Note the following when loading the machine with fuel:
❒ Only use permitted fuels!
⇨ See "Permitted fuels" [page 7]
❒ Remove foreign bodies from the store before filling
NOTICE! Systems in which the fuel is delivered by tanker and is blown into the store
space must be fitted with a rotary valve.
CAUTION
Entering the store space when the system is switched on
Risk of injury due to automatic startup of system, particularly the discharge
system!
Therefore, before entering the fuel store:
❒ Switch off the power supply to the entire system
➥ Depending on the model via boiler, expansion switch cabinet, etc.
For blowing in fuel the following precautions also apply:
CAUTION
Blowing in fuel when the boiler is switched on:
The underpressure generated from blowing in fuel can lead to smoke being
sucked back into the store if the boiler is switched on. Possible excess pressure
could cause smoke to escape into the installation room, possibly resulting in injury
and damage!
Therefore, before blowing in the fuel:
❒ Switch off the power supply to the entire system
➥ Depending on the model via boiler, expansion switch cabinet, etc.
❒ Allow the system to cool for at least two hours