10.2      Troubles and causes of remote controller

10.3      Malfunctions and malfunction code

If anything happens like the situation described below, please shut off the power supply of 

the unit  and contact with the custormer service center immediately.

(× Extinguish,   Flash at 5Hz)

Before asking for serving or repairing, check the following points. 

(see in table 10-2)

table 10-2

Symptoms

Causes

Solution

The fan speed can not be changed.

   Check whether the MODE indicated 

on the display is "AUTO"

When the automatic mode is selected, the 
air conditioner will automatically change 
the fan speed.

   Check whether the MODE indicated 

on the display is "DRY"

When dry operation is selected, the air 
conditioner automatically change the fan 
speed. The fan speed can be selected 
during "COOL", "FAN ONLY", and "HEAT".

The remote controller signal is not 
transmitted even when the ON/OFF 
button is pushed.

   Check whether the batteries in the 

remote controller are exhausted.

The power supply is off.

The TEMP. indicator does not come 
on. 

   Check whether the MODE indicated 

on the display is FAN ONLY

The temperature cannot be set during 
FAN mode.

The indication on the display 
disappears after a lapse of time.

   Check whether the timer operation 

has come to an end when the 
TIMER OFF is indicated on the 
display.

The air conditioner operation will stop up 
to the set time 

The TIMER ON indicator  goes off 
after a lapse of certain time.

   Check whether the timer operation 

is started when the TIMER ON is 
indicated on the display.

Up to the set time, the air conditioner will 
automatically start and the appropriate 
indicator will go off.

No receiving tone sounds from the 
indoor unit even when the ON/OFF 
button is pressed.

   C h e c k   w h e t h e r   t h e   s i g n a l 

transmitter of the remote controller 
is properly directed to the infrared 
signal receiver of the indoor 
unit when the ON/OFF button is 
pressed.

Directly transmit the signal transmitter 
of the remote controller to the infrared 
signal receiver of the indoor unit, and then 
repeatly push the ON/OFF button twice. 

NO.

Malfunction

running lamp

timer lamp

defrosting lamp

alarm lamp

alarm lamp

1

Room temperature sensor 

checking channel is abnormal

×

×

×

E2

2

Evaporator sensor checking 

channel is abnormal

×

×

×

E3/E4

3

EEPROM malfunction

×

×

E7

4

Water-level switch malfunction

×

×

×

E8

Содержание KFC-CI-2T-300D1

Страница 1: ...ng your air conditioner please read this manual carefully and keep it for future reference INSTALLATION OWNER S MANUAL Fancoil Four way Cassette Type MKD V300 V1 KFC CI 2T 300D1 MKD V500 V1 KFC CI 2T...

Страница 2: ......

Страница 3: ...the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry Before obtaining access to terminals all s...

Страница 4: ...install the air conditioner in the following locations There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near...

Страница 5: ...hook 4 4 2 Installation hook 4 4 3 Installation paper board 1 1 4 Bolt M6 4 Tubing Fittings 5 Soundproof insulation sheath 2 2 Drainpipe Fittings 6 Out let pipe pipe 1 1 7 Out let pipe sheath 1 8 Out...

Страница 6: ...Install the main body Face the concave side of the installation hooks toward the expansible hooks Determine the length of the installation hooks from the height of ceiling then cut off the unnecessary...

Страница 7: ...ner insulation Insulation local Central hole Grid switch All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend o...

Страница 8: ...pipe joint Connecting point of drain pipe Ground Ground Panel Panel Outlet Outlet 600mm ceiling hole 600mm ceiling hole Outlet Outlet Inlet Inlet Unit mm Tubing side FIGURES 3 Fig 5 12 Fig 5 13 Fig 5...

Страница 9: ...then drainpipe apply protective tube to wrap its indoor parts for ensuring the lengthen part connected tightly 7 In case the drainpipe outlet is higher than pumping connective pipe of the main body th...

Страница 10: ...1 0m Lean over 1 100 Lean over 1 100 Pump pipe clasp the fittings Pump pipe clasp the fittings Max 1000mm Max 600mm Fig 6 1 Fig 6 2 0 8 1 0 m 1 0 m a b 5 Turn off the power drain the water away The d...

Страница 11: ...ther the switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver moves normally d Whether the room temperature is adjusted we...

Страница 12: ...mild detergent to clean it and dry out in cool place Caution Do not dry out the air filter under direct sunshine or with fire The air in side should face up when using vacuum cleaner See fig 9 3 The...

Страница 13: ...ies of remote controller exhausted or other problem of controller Wait for the comeback of power Switch on the power Replace the fuse Replace the batteries or check the controller Air flowing normally...

Страница 14: ...cated on the display is FAN ONLY The temperature cannot be set during FAN mode The indication on the display disappears after a lapse of time Check whether the timer operation has come to an end when...

Страница 15: ...lamp defrosting lamp alarm lamp 1 Room temperature sensor checking channel is abnor mal X X X 2 Evaporator sensor checking channel is abnormal X X X 3 EEPROM malfunction X X 4 Water level switch malf...

Страница 16: ......

Отзывы: