4
2. Prepare the following assemblies on the site.
Note to installation of GW-KNX(A) - (K05-KNX 01 A):
1. One KNX module can only connect with one indoor unit;The KNX module should
connect to indoor D1D2E ports.
2. Circuit of GW-KNX(A) - (K05-KNX 01 A) is low voltage circuit. Never connect
it with a standard 220V/380V circuit or put it into a same Wiring Tube with the
circuit.
3. Do not attempt to extend the shield cable by cutting, if it is necessary, use
Terminal Connection Block to connect.
4. After finishing connection, do not use Megger to have the insulation check to the
signal wire.
5. The default physical address of the GW-KNX(A) - (K05-KNX 01 A) is 15.15.255,If
there are two or more KNX modules, then the physical addresses can not repeat.
The physical address can be changed by ETS software.
No.
Name
Qty.(embeded
into wall)
Specification (only
for reference)
Remarks
1
2-core shielded cable
1
RVVP-0.5mm
2
x2
Max 350m
2
86 Electrician box
1
3
Wiring Tube(Insulating
Sleeve and Tightening
Screw)
1
4
KNX power module
1
5
Communicate module
1