9
Function
Group
Address Length
Data Type
Function Attribute
Remarks
Set room
temperature in
heating mode
0/0/23
2 bytes
F16/Float
Output
CRT
ºC
Current room
temperature in
heating mode
0/0/24
2 bytes
F16/Float
Output
CRT
ºC
Set temperature
in water heating
mode
0/0/25
2 bytes
F16/Float
Output
CRT
ºC
Current
temperature in
water heating
mode
0/0/26
2 bytes
F16/Float
Output
CRT
ºC
Enabling the water
heating mode and
heating mode
0/0/27
1 byte
Output
CRT
0: Default value
1: Enabling the
heating mode and
water heating mode
2: Water heating
mode, without heating
mode
3: Heating mode, with
water heating mode
Current control
status in heating
mode
0/0/28
1 byte
N8/
Enumeration Output
CRT
0: Default value
1: Water outlet
temperature control is
valid
2: Room temperature
control is valid
Содержание GW-KNX(A)