COMPONENT TESTING
Touch Test Chart : To Service Reversing Valves
DISCHARGE
TUBE
from Compressor
Tube to INSIDE
T
ube to INSIDE
Capillary
T
ube
RIGH
T Pilot
Capillary
T
ube
Capillary Tube
LEF
T Pilot
SUCTION
to Compressor
TUBE to
Compressor
Capillary Tube
COI
L
14
COIL
NORMAL FUNCTION OF VALVE
VALVE
OPERATING
from Compressor
DISCHARGE TUBE
SUCTION TUBE
COIL
Tube to OUTSIDE
LEFT Pilot
RIGHT Pilot
CONDITION
NOTES:
1
2
3
4
6
5
POSSIBLE CAUSES
* TEMPERATURE OF VALVE BODY
** WARMER THAN VALVE BODY
Hot
Normal Cooling
CORRECTIONS
Cool
Cool
as (2)
Hot
as (1)
*TVB
TVB
Normal Heating
Hot
Cool
Hot
as (1)
Cool
as (2)
*TVB
TVB
MALFUNCTION OF VALVE
Valve will not
to heat.
shift from cool
Check Electrical circuit and coil
Repair electrical circuit.
No voltage to coil.
Replace coil.
Defective coil.
Check refrigeration charge
Repair leak, recharge system.
Low charge.
Pressure differential too high.
Recheck system.
Hot
Cool
Cool,
as (2)
Hot,
as (1)
Hot
*TVB
Pilot valve okay. Dirt in one bleeder hole.
Piston cup leak
Deenergize solenoid, raise head pressure,
reenergize solenoid to break dirt loose.
If unsuccessful, remove valve, wash
out. Check on air before installing. If no
movement, replace valve, add strainer to
discharge tube, mount valve horizontally.
Valve will not
Stop unit. After pressures equalize, restart
with solenoid energized. If valve shifts,
reattempt with compressor running. If still
no shift, replace valve.
shift from cool
to heat.
Hot
Cool
Cool,
as (2)
Hot,
as (1)
*TVB
*TVB
Clogged pilot tubes.
Raise head pressure, operate solenoid to
free. If still no shift, replace valve.
Hot
Cool
Cool,
as (2)
Hot,
as (1)
Hot
Hot
Both ports of pilot open. (Back seat port
did not close).
Cool
Warm
Raise head pressure, operate solenoid
to free
partially clogged port. If still no shift,
replace
valve.
Cool,
as (2)
Hot,
as (1)
*TVB
Warm
Defective Compressor.
Replace compressor
Starts to shift
complete
reversal.
but does not
Hot
Warm
Warm
Hot
Hot
*TVB
Check unit for correct operating pressures
and charge. Raise head pressure. If no
shift, use valve with smaller port.
Not enough pressure differential at start
of stroke or not enough fl ow to maintain
pressure differential.
Replace valve
Body dama ge.
Hot
Warm
Warm
Hot
Hot
Hot
Both ports of pilot open.
Raise head pressure, operate solenoid. If
no shift, use valve with smaller ports.
Replace valve
Body damage.
Hot
*TVB
Hot
Hot
Hot
Hot
Hot
Hot
Raise head pressure, operate solenoid. If
no shift, use valve with smaller ports.
Hot
Hot
Valve hung up at mid-stroke. Pumping
volume of compressor not suf fi cient to
maintain reversal.
Hot
Hot
Both ports of pilot open.
Apparent
Raise head pressure, operate solenoid.
If no
shift, replace valve.
leap in heat-
ing.
Hot
Cool
Hot,
as (1)
Cool,
as (2)
*TVB
*TVB
Piston needle on end of slide leaking.
Hot
Cool
Operate valve several times, then recheck.
If excessive leak, replace valve.
Hot,
as (1)
Cool,
as (2) **WVB
**WVB
Pilot needle and piston needle leaking.
Operate valve several times, then recheck.
If excessive leak, replace valve.
Will not shift
cool.
from heat to
Hot
Cool
Hot,
as (1)
Cool,
as (2)
*TVB
*TVB
Pressure differential too high.
Clogged pilot tube.
Stop unit. Will reverse during equalization
period. Recheck system
Hot
Raise head pressure, operate solenoid to
free dirt. If still no shift, replace valve.
Cool
Hot,
as (1)
Cool,
as (2)
Hot
*TVB
Dirt in bleeder hole.
Hot
Cool
Hot,
as (1)
Cool,
as (2)
Hot
Raise head pressure, operate solenoid.
Remove valve and wash out. Check on air
before reinstalling, if no movement, replace
valve. Add strainer to discharge tube.
Mount valve horizontally.
Piston cup leak.
*TVB
Hot
Cool
Hot,
as (1)
Stop unit. After pressures equalize, restart
with solenoid deenergized. If valve shifts,
reattempt with compressor running. If it
still will not reverse while running, replace
the valve.
Cool,
as (2)
Replace valve.
Defective pilot.
Hot
Hot
Warm
Cool
Warm,
as (1)
Cool,
as (2) Warm
*TVB
Defective compressor.
Replace compressor
Figure 603 (Reserving Valve)
Содержание VRP12K
Страница 30: ...30 OPERATION FreshAire Control To engage the FreshAire system flip the switch into the ON position ...
Страница 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Страница 47: ...47 OPERATION Component Identification Indoor Blower BLDC Counter Clockwise Impeller 600 1300 RPM ...
Страница 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Страница 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Страница 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Страница 177: ...177 UPDATING VRP FIRMWARE Or ...
Страница 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Страница 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Страница 194: ...194 UPDATING VRP FIRMWARE Retrieving VRP Data Right Click Data txt Send to Compressed zipped folder ...
Страница 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Страница 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Страница 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Страница 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Страница 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...
Страница 214: ...214 PARTS CATALOG 36k Control Box Diagram Figure 906 12 12 11 13 10 8 4 3 2 16 5 6 7 1 9 10 9 10 11 11 14 15 ...