background image

STEP 1: CUT OPENING IN GASKET

Remove an 8" portion of the weather seal gasket from the bottom left surface of the plenum.  
To remove: Cut the gasket in the lower left corner of the plenum. Then make a second cut 8" from the left 

corner. The gasket should peel away from the plenum leaving a clean mounting surface (See detail A).

STEP 2: SEAL AND SET PAN

Prior to placing the drain pan into the opening run a 1/4" bead of sealant the entire width of the removed 

gasket. The secondary overflow lip must extend into the plenum to prevent water leaks. The pan should 

be mounted against the 3/4" flange of the plenum, refer to view A.

A

DETAIL A

8.00

B

2.00

A

Sealant

920-150-01 (8-17)

Installation Instructions

DRAIN PAN

For VEA24, VHA18, and VHA24 units only.

Please read these instructions completely before attempting installation.

NOTE: 

This drain pan must be installed with all VEA24, VHA18 and VHA24 units.

Model VPDP1