105
PB
TROUBLESHOOTING
IPM Protection, Out-of-Step Fault, Compressor Phase Overcurrent
If the connection between control panel AP1 and compressor COMP is secure? If loose? If the connection is in correct order?
If the voltage input of the machine is within normal range? (Use AC voltmeter to measure the voltage between terminal L and N on the
wiring board XT)
If the compressor coil resistance is normal? If the insulation of compressor coil against the copper tube is in good condition?If
the working load of the machine are too high? If the radiation is good?
If the charge volume of refrigerant is correct?
(AP1 below refers to the outdoor control panel)
Energize and
switch on
IPM protection
occurs after the
machine has run for
Please confirm:
a period of time?
1. If the indoor and outdoor heat exchangers are dirty? If they are obstructed by other objects which affect the
heat exchange of indoor and outdoor unit.
2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high, resulting in that the system pressure is too high and exceeds the
permissible range?
4. If the charge volume of refrigerant is too much, resulting in that the system pressure is too high?
5. Other conditions resulting in that the system pressure becomes too high.
then energize and start
the unit.
If there is any
abnormality
Take corrective actions
according to Technical
Service Manual, and
described above?
Replace the
If the connection
control panel AP1
between AP1 and
COMP is unsecure
or the connection
order is wrong?
Connect the control panel
AP1 and compressor
COMP correctly according
to the Electrical Wiring
Diagram. Then, energize
and start the unit.
Service Manual.
compressor resistance on
If the
resistance is
normal?
Use ohmmeter to
measure the resistance
between the three
terminals on compressor
COMP, and compare the
measurements with the
Use ohmmeter to
measure the resistance
between the two
terminals of compressor
COMP and copper tube.
Replace the
compressor
COMP
Resistance higher
than 500
MΩ
?
Replace the
AP1
control panel
END
If the unit can
worknormally?
Y
Y
N
N
If the unit can
normally?
work
Y
Y
Y
N
Y
N
Refer to the
Electrical Wiring
Diagram and check
if the connection
between AP1 and
COMP is loose and if
the connection order
is correct.
Содержание MRM09Y1J
Страница 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Страница 37: ...37 OPERATION 18 24kSequenceofOperation...
Страница 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Страница 39: ...39 OPERATION 18 24k Sequence of Operation...
Страница 40: ...40 OPERATION 18 24k Sequence of Operation...
Страница 41: ...41 OPERATION 18 24k Sequence of Operation...
Страница 47: ...47 INSTALLATION...
Страница 48: ...48 INSTALLATION Installation Tools...
Страница 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Страница 113: ...113 WIRING DIAGRAMS Figure 804 36K Indoor Unit Wiring Diagrams Figure 803 24K Indoor Unit Wiring Diagram 6361000043101...
Страница 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Страница 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Страница 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Страница 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Страница 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...
Страница 130: ...130 PARTS CATALOG Outdoor Unit MRMY36J FIgure 907 2 9 10 18 20 21 11 12 14 15 22 23 26 27 32 34 4 1...