17
PB
OPERATION
Function and Control
Buttons and Display
1) Buttons
There are ON/OFF, UP, DOWN, HEAT, COOL, CONSTANT FAN and fan speed of HIGH, LOW, AUTO buttons.
1. ON/OFF: Press to turn power on or off to the unit.
2. COOL, HEAT: choose the mode of operation
3. HIGH, LOW, AUTO: choose the fan speed.
4. UP, DOWN: Adjust the setting temperature , default: 60-90
°F
(16~32
°
F).
2) Dual 8 Digital Tube Displayer and LED
Two 8 digital tube and 7 LEDs (ON/OFF, HIGH, LOW, AUTO, HEAT, COOL, CONSTANT FAN)
1. Mode LED display: when the unit is running in a certain mode, the corresponding LED is lit up.
2. ON/OFF LED: at ON status, the LED is lit up.
3. CONSTANT FAN LED: when this function is enabled, the LED is lit up.
4. Fan speed LED: when the unit is running at HIGH, LOW or AUTO fan speed, the corresponding LED is
litup.
5. Dual 8 digital tube displayer: normally, it displays the indoor ambient temperature. When the UP/DOWN
button is pressed it displays the setting temperature. When some error occurs, it displays the ERROR
CODE.
Temperature Definition
Indoor setting temperature (Ts)
Indoor ambient temperature (T1)
Indoor coil temperature (T2)
Outdoor coil temperature (T3)
Outdoor ambient temperature (T4)
Compressor discharge temperature (T5)
Indoor outlet air temperature (T6)
System Basic Function
Once the compressor starts, the compressor won’t stop with the change of the indoor temperature. Once the
compressor stops, it can only start after a 3 mins delay. (The compressor can stop immediately at the time of
mode switchover, turning off the unit, adjusting setting temperature and turning off from a function error.)
Depending on the different ambient temperatures and setting temperatures, the compressor runs at different
frequencies to achieve the best energy savings and comfort. This is the advantage over traditional A/C compressors.
1) Cooling Mode
Working conditions and process for cooling:
When
T1
≥
Ts+2
°
F(1
°
C), cooling turns on.
When
T1
≤
Ts-2
°
F(1
°
C), cooling turns OFF.
When Ts- 2
°
F(1
°
C)<T1<Ts+ 2
°
F(1
°
C), the unit keeps previous running status.
Indoor fan control in cooling mode:
The indoor fan will run synchronously with cooling demand. During no demand period if the CONSTANT
FAN button is turned off, it will run for 30s and then turn off..When CONSTANT FAN is ON, it will always be
running.
Outdoor fan control in cooling mode:
The outdoor fan has two speeds, low and high. When T4 is above 80
°
F, the fan operates in high speed.
When T4 drops to 77
°
F the fan operates in low speed.
2) Heating Mode
Working conditions and process for heating:
When
T1
≤
Ts -2
°
F(1
°
C), the unit is running in heating mode. The heat pump or electric heating will start
depending on the ambient temperature condition.
When
T1
≥
Ts+ 4
°
F(2
°
C), the heating is turned OFF.