Rittal Liquid Cooling Package
47
11 Technical specifications
11
11.4 High temperature condenser for ambient temperatures up to +53 °C
Cooling circuit
Coolant/Fill volume [kg]
R410A/see tab. 22 "Total refrigerant charge"
Connection diameter refrigerant pipes [mm]
See tab. 23 "Refrigerant pipes"
External diameter of coolant lines [mm]
See tab. 23 "Refrigerant pipes" (1mm wall thickness)
Other information
Storage temperatures [°C]
-40…+50
Ambient temperature [°C]
-40…+45
Technical specifications
Description/Model No.
High temperature condenser
Dimensions and weight
Dimensions W x H x D ("H" version) [mm]
2225 x 1046 x 900
Dimensions W x H x D ("V" version) [mm]
2206 x 830 x 570
Weight, max. [kg]
104
Electrical connection
Type of electrical connection
Connection clamp
Rated voltage [V, Hz]
230/1~/N/PE, 50
230/1~/N/PE, 60
Startup current [A]
2
2
Pre-fuse T [A]
6
6
Duty cycle [%]
100
Cooling circuit
Coolant/Fill volume [kg]
R410A/see tab. 22 "Total refrigerant charge"
Connection diameter refrigerant pipes [mm]
See tab. 23 "Refrigerant pipes"
External diameter of coolant lines [mm]
See tab. 23 "Refrigerant pipes" (1mm wall thickness)
Other information
Storage temperatures [°C]
-20…+55
Ambient temperature [°C]
-20…+53
Noise level [dB(A)]
(Open air above reflective flooring, distance 10 m)
40
Tab. 21:
Technical specifications for the high temperature condenser unit
Technical specifications
Tab. 20:
Technical specifications for the winter kit module