Rittal Liquid Cooling Package
33
7 Operation
7
7.13.5 LCP DX supervisory table
Tab. 14:
LCP DX supervisory table – analogue variables
BMS Ad-
dress
Description
UOM
Min
Max
Read/
Write
Note
1
Reserved – (not used or other special appli-
cation or internal debug)
°C
-99.9
99.9
R
Only for Service/
Manufacturer
2
B2 probe value: LCP Server IN
°C
-99.9
99.9
R
Customer
3
B3 probe value: LCP Server IN
°C
-99.9
99.9
R
Customer
4
B4 probe value: LCP Server IN
°C
-99.9
99.9
R
Customer
5
Reserved – (not used or other special appli-
cation or internal debug)
°C
-99.9
99.9
R
Only for Service/
Manufacturer
6
B6 probe value: ROOM Server OUT
°C
-99.9
99.9
R
Customer
7
B7 probe value: ROOM Server OUT
°C
-99.9
99.9
R
Customer
8
B8 probe value: ROOM Server OUT
°C
-99.9
99.9
R
Customer
9
B9 Probe value: Compressor discharge
temperature
°C
-99.9
99.9
R
Customer
10
B10 Probe value: Compressor suction tem-
perature
°C
-99.9
99.9
R
Customer
11
B11 probe value: High pressure – Compres-
sor Discharge Pressure
bar
-99.9
99.9
R
Customer
12
B12 probe value: Low pressure – Compres-
sor Suction Pressure
bar
-99.9
99.9
R
Customer
13
Evaporator temperature from Low pressure
conversion
°C
-99.9
99.9
R
Customer
14
Condensing temperature from High pres-
sure conversion
°C
-99.9
99.9
R
Customer
15…20
Reserved – (not used or other special appli-
cation or internal debug)
–
–
–
–
Only for Service/
Manufacturer
21
Server Medium Temp Out – (Room)
°C
-99.9
99.9
R
Customer
22
Server Medium Temp In – (LCP)
°C
-99.9
99.9
R
Customer
23…44
Reserved – (not used or other special appli-
cation or internal debug)
–
–
–
–
Only for Service/
Manufacturer
45
Compressor Rotor speed
rps
0
999.9
R
Customer
46
Compressor Motor current
A
0
99.9
R
Customer
47
Reserved – (not used or other special appli-
cation or internal debug)
rps
0
999.9
R
Only for Service/
Manufacturer
48
Main Setpoint LCP
°C
-99.9
99.9
R/W
Customer
49…207
Reserved – (not used or other special appli-
cation or internal debug)
–
–
–
–
Only for Service/
Manufacturer