Pamir 3500/4200/5000
22
EN
Start-up (E)
When the unit is used for the first time or after
a long period of non-use, smoke or an odour
may result from dust or dirt which has collected
on the element. This is completely normal and
disappears after a short time.
*
1
) 2 m and 2.5 m units are connected with two power
supplies. The 2.5 m unit has electric coils with two
different outputs, and the coil to the left, on the horizontal
unit, viewed from inside the premises, has the highest
output.
*) Dimensioning of external wiring shall comply with
applicable regulations and local deviations may occur.
Control
Type
Output Voltage Minimum
area*
Electrical installation
The installation, which should be preceded by
an isolator switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
The air curtain has an intregrated PC board
which is connected to the selected external
control system FC. FC must be ordered
separately. The PC board is accessed via cable
glands on the top of the unit (horizontal) or
on the back (vertical). See Fig. 2. FC is supplied
pre-programmed. Communication- and sensor
cables are connected to the PC board.
Should more than one air curtain be
controlled by a single FC, an additional
communication cable FCBC per unit will be
required. See manual for FC.
Unit without heating or with water heating
The electrical connection is made on the
top of the unit (horizontal) or on the back
(vertical). Pierce the gland with a screwdriver
before entering the cable. See Fig. 2. Control is
supplied by 230V~ to the PC board.
Unit with electrical heating
The electrical connection is made on the
top of the unit (horizontal) or on the back
(vertical). Pierce the gland with a screwdriver
before entering the cable. See Fig. 2. Control
is supplied by 230V~ to the PC board. Power
supply for heating (400V3~) is routed via the
motor compartment, secured with preinstalled
cable ties, and connected to the terminal block
in the terminal box. 2-metre and longer units
require dual power supplies. See dimension
drawings.
The largest cable diameter for the terminal
block is 16 mm². The cable glands used must
meet the protection class requirements. In the
distribution board, it is to be indicated that ”the
air curtains can be supplied from more than
one connection”.
Vertical mounting
Units from 1,5 metres and longer may be used
vertically. The air curtain is mounted vertically
as close as possible to the door. For the best
effect air curtains should be placed on both
sides of the opening.
For vertical mounting, each unit must be
supplemented with a vertical kit PA3JK/PA4JK.
The unit can be reversed and placed on either
side of the door. Connections and PC Board are
positioned near floor level when the air curtain
is placed to the left of the door and at the top
when it is placed to the right (seen from the
inside). See fig. 11 and separate manual.
The air curtain is mounted on a floor frame
that is included in the vertical kit. The frame
is attached horizontally to the floor using
fasteners appropriate for the surface.
Max two units can be mounted directly on top
of each other, the floor frame is then used as a
joining bracket.
Note! The air curtain must be secured in the
wall or ceiling. Fasteners are not included.
A design kit that provides a neater installation
for concealing cables and pipes is available as
an accessory, see accessories pages.