VYPER
™
VARIABLE SPEED DRIVE
OPERATION
100-210 IOM (
JUL
09)
Page 43
Figure 43 - Vyper™ Screen
VYPER SCREEN SETPOINTS
The Vyper
™
Screen
(See Figure 43) contains setpoints and
information pertinent to the operation of the Vyper
™
such as
internal currents, voltages, and temperatures. This screen also
gives detailed information on some external equipment such
as the circulation pump and the motor temperature.
The Service Level 2 Vyper
™
Screen is similar to Level 1, but
adds the capability of adjusting several setpoints, as follows:
Standby Time:
The VSD enters Standby mode when there
is no load on the VSD. The VSD capacitor banks remain
charged and the compressor output is 0 Hz. Standby mode
permits fast acceleration when the load returns. If the time
of zero load surpasses the Standby Time setting, the VSD
will need to go through a restart sequence. The values for
Standby mode can be set from 20 to 120 minutes.
Clear Standby Time:
This option can be pressed to clear the
Standby time value from the VSD if not desired.
Clear VSD Memory:
Clear the existing trending values in
the Vyper
™
memory.
Clear Total kWh:
This function clears the accumulated kWh
totals from the counter since the last reset. The value returns
to zero upon selecting this option.
The following Vyper
™
screen parameters display measured
values in accordance with the user defined unit selections.
•
Average Current (Amps)
•
Current Phase A (Amps)
•
Current Phase B (Amps)
•
Current Phase C (Amps)
•
Full Load Amps (%)
•
Output Frequency (Hz)
•
Output Voltage (Volts)
•
DC Bus Voltage (Volts)
•
Input Power (kW)
•
Current Value Timer (Min:Sec)
•
Actual Speed (RPM)
•
Speed Command (RPM)
•
Ambient Temperature (°F or °C)
•
Converter Heatsink Temp (°F or °C)
•
Baseplate Temperature (°F or °C)
•
Job FLA (Amps)
•
DC Inverter Link Current (Amps)
•
Motor Temperature (°F or °C)
•
VSD Model (305 or 435)
•
Total kWh (kWh)
The status of the following parameters are indicated using a
binary number next to the field description. Table 14 describes
the status of the parameter indicator.
Indicator
Status
“0”
no /off
“1”
yes / on
Table 14 – Binary Parameter Indicator Status
•
VSD Operating Mode
•
Harmonic Filter Present
•
Harmonic Filter Operating Mode
•
Water Pump Energized
•
Precharge Relay Energized
•
Trigger SCRs Energized
NOTE: Repetitive/Unexplained Vper Cutouts - For repeti-
tive or unexplained cutouts, tab to the [Clear Standby
Time] button and clear by pressing the enter button.
Repeat that process to also clear the [Clear VSD Memory]
and [Clear Total KWH] buttons.