Frick Vyper 254 Скачать руководство пользователя страница 6

VYPER

 VARIABLE SPEED DRIVE

INSTALLATION

100-200 IOM (FEB 09)

Page 6

-- Apply power to the Vyper Drive system. 

  A: Confirm dipswitches on the Vyper Logic Board are properly set. Refer to the “VSD Logic Board Setup” section of the 

S100-200 or S100-210 IOM.

  B: Verify no problems exist with the unit power supply connections.
  C: Verify no problems exist with the boot-up of the Quantum

LX panel and control system.

  D: Set the FLA ratings on the Vyper Logic Board as per job site requirements.
  E: Set up the Quantum

LX panel in accordance with job site requirements. Refer to Refer to Quantum

LX Panel Setup in 

the Operation portion of the S100-200 or S100-210 IOM.

  F: Confirm operation of internal cooling fans.
  G: Confirm operation of the coolant pump.
  H: Confirm operation of the Vyper motorized coolant temperature control mixing valve. 
  I:  Confirm wiring, operation, and correct rotation of motor blower fans if present.

Pre-startup Inspection

After  installation  is  complete,  use  the  following  as  guide 

to checks items D – I, under in the Applying power to the 

Vyper

 Drive system section, in the preceding Vyper

 Pre-

Operation Site Checklist. Any changes to factory setpoints, 

needs to be approved by Frick

®

. Failure to obtain approval 

may void warranty. Read all steps thoroughly and contact 

the factory with any questions before proceeding. 

1.  With  power  off  -  In  the  drive,  remove  wire  624  (com-

pressor run) on the drive side of control wiring terminal 

strip. 

2.  Remove wire 675 (oil pump run) if the unit is equipped 

with an oil pump.

3.  Close the drive, turn on the disconnect using the oper-

ating handle on the door.

4.  Once the Quantum

LX panel has booted go to the level 

2 operating session.

5.  Confirm  communications  between  the  Vyper

  drive 

and  the  Quantum

LX  by  going  to  the Vyper

  screen. 

If  there  are  base-plate  temperature  readings  that  are 

approximate to ambient and a value is displayed for the 

JOB  FLA  communications  is  confirmed.  Compare  the 

Job FLA value to the panel test report Special Instruc-

tions section to ensure they match. If the JOB FLA is not 

listed on the panel test report, use the JOB FLA tables 

in this manual to calculate.

6.  Go  to  the  motor  setpoints  screen  to  check  the  motor 

amps safeties, relative to the motor and drive combina-

tion. If these values are not correct use the tables in this 

manual to calculate what they should be.

7.  Verify proper operation of the motorized coolant mixing 

valve on the back of the drive. 

 

•  Locate the Coolant mixing valve on the back of the 

drive,  remove  the  cover  from  the  motor  and  check 

that the dip-switches are set as 1 ON, 2 OFF, 3 ON 

& 4 OFF. If a change needs to be made, the power 

must be cycled at the panel for the change to be in 

effect. 

 

•  Go to Page 2 of PID setpoints, for the Vyper Coolant 

PID. Ensure the setup is per the setup in this manual. 

If it is, set the Control as Always and the Direction 

as Reverse. Check the indicator disc or arrow on the 

shaft between the valve and the actuator motor that 

it is operating. Once it has moved to one end of the 

stroke,  change  the  Direction  back  to  Forward. This 

should move the Indicator Disc or Arrow back to the 

other end of the stroke. 

 

•  Set the Control back to Running and submit.

8.  Using  a  screw  driver  at  the  operating  handle  on  the 

door, open the drive leaving the power on, so that the 

ride side panel can be opened providing access to the 

logic board.

9.  Re-secure the left side panel.

10. If the Job FLA setting is not correct this can now be set 

using the Job FLA pot on the control logic board. Moni-

tor the value on the Vyper screen of the Quantum

LX to 

determine when the value is properly set.

11. Test the internal fan and coolant circulation pump op-

eration by removing the P2 plug from the J2 connector 

on the control logic board. Removing this plug will start 

these devices. You will hear the fans run. The circulation 

in  the  coolant  loop  should  be  seen  through  the  clear 

hose, proving the circulation pumps operation. Recon-

nect the P2 plug to the J2 connector to turn off these 

devices. Doing this test will create a Low Inverter Base-

Plate Temperature shutdown on the Quantum

LX that 

will need to be cleared.

12. Close the drive completely and with power still on, do a 

simulated run of the compressor by pressing the manu-

al start button on the Quantum

LX. This should engage 

the  blower  motors  on  the  compressor  drive  motor  to 

verify proper rotation and operation of the blower mo-

tors. Rotational arrows on the fan housing shows proper 

rotation, correct if necessary by changing any two wires 

at the blower motor connection box with power locked 

out.

13. Turn power off with the operating handle on the door of 

the drive. Open the drive and check to ensure the panel 

is  de-energized.  Carefully  replace  wires  624  and  675. 

Tighten to 12 lb. In.

Содержание Vyper 254

Страница 1: ...3c THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN DAMAGE OR IMPROPER OPE...

Страница 2: ...IPMENT 11 INTERFERENCE WITH ELECTRONIC EQUIPMENT 12 SYSTEM OPERATING CONDITIONS 12 PNEUMATIC CONTROLS 12 VYPER SYSTEM OVERVIEW 12 CONFIGURATION 16 VYPER COOLING LOOP 16 Liquid Cooled Vyper P I Diagram...

Страница 3: ...ctronic con trol equipment All safety precautions consistent with opera tion of high current and voltage electrical equipment should be strictly enforced JOB INSPECTION Immediately upon arrival examin...

Страница 4: ...GING AND HANDLING The Vyper cabinet unit is best moved via lifting lugs on the top sides of the cabinet Special care must be exercised not to damage the pump or peripheral equipment on the rear of the...

Страница 5: ...and Frick publication S90 400 SB Verify that all control power 120 VAC communications analog wiring and 460 VAC power are in separate metallic con duits Properly shielded and grounded analog cables a...

Страница 6: ...e the tables in this manual to calculate what they should be 7 Verify proper operation of the motorized coolant mixing valve on the back of the drive Locate the Coolant mixing valve on the back of the...

Страница 7: ...operating frequency range of the drive The unit is started with the compressor fully unloaded until the frequency reaches the minimum operating frequency range In addition the drive is capable of ope...

Страница 8: ...0 feet Adequate service clearances including door swing must be maintained around the Vyper Care should be taken to ensure that the Vyper and it s associated piping and wiring do not obstruct the acce...

Страница 9: ...ER PRESSURE DROP In order to adequately size piping and booster pump require ments the pressure drop of the coolant across the heat Figure 3 Minimum Flow Rates GLYCOL exchanger must be known Figure 4...

Страница 10: ...tions regarding disconnect devices conductor sizes wire types and circuit protection Unshielded cable is acceptable if it can be separated from sensitive circuitry Allow a spacing of 12 inches for eve...

Страница 11: ...r at all operational loads and conditions Capacitors can be located at one or several places on a distribution system Solid state motor controllers may not run or have difficulty starting in that scen...

Страница 12: ...odes One SCR and one diode are contained in each module Three modules are required to covert the three phase input AC voltage to DC voltage 1SCR 3SCR The modules are mounted on a liquid cooled heatsin...

Страница 13: ...SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 13 Figure 6 Vyper Elementary Wiring Diagram NOTE Drawings for specific units can be found in the door of the Vyper drive or check with Frick Engineeri...

Страница 14: ...sure that the IGBT transistor module does not rupture if a failure were to occur on the DC link of the Filter Power Unit THETHREE PHASE INDUCTOR provides some impedance for the filter to work against...

Страница 15: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 15 Figure 8 Harmonic Filter Elementary Wiring Diagram NOTE Typical Check with engineering for latest drawings...

Страница 16: ...nd shutdowns as sociated with theVyper coolant temperature reading These wil also be factory set for a Low Temp alarm and shutdown at 85 F and 80 F with a 90 second delay when running The High Temp Al...

Страница 17: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 17 Liquid Cooled Vyper P I Diagram Economized...

Страница 18: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 18 Liquid Cooled Vyper P I Diagram Noneconomized...

Страница 19: ...The Vyper cabinet is mounted on a rectangular welded steel channel which provides both an attachment point for the cabinet s side brackets and also helps to maintain the rigidity of the cabinet durin...

Страница 20: ...Page 20 BLOWER MOTOR ROTATION The Blower Motor rotation is marked on the blower assembly and is to be such that the blower draws into the assemly through the screen and pushes down and through the mot...

Страница 21: ...Page 21 Dimensions in Inches Drive HP A B C D E F G H J K 305 254 1 63 4 50 9 00 6 38 4 38 35 00 5 50 3 56 6 63 2 00 437 362 6 63 6 75 10 13 2 00 3 25 40 53 2 25 3 00 13 00 2 00 Contact factory for de...

Страница 22: ...in that the Drive has been powered down for at least five minutes This allows the internal capacitors resistors to discharge the DC bus and allow for safe maintenance of the unit Failure to do so may...

Страница 23: ...ion 216 240 in lb ELECTRICAL CONDUITS All power wiring must be contained in metallic conduit All compressor motor wiring must be in a separate metallic conduit Oil pump motor wiring must be in a separ...

Страница 24: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 24 MOTOR RTD THERMAL PROTECTION Figure 17 TEMPERATURE CONTROL VALVE WIRING Figure 18...

Страница 25: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 25 MOTOR COOLING BLOWER WIRING Figure 19 Figure 20 DRAWING NOTES...

Страница 26: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 26 ANALOG BOARD WIRING Figure 21...

Страница 27: ...ans c Confirm operation of coolant circulation pump d Confirm wiring and operation of the motor blower fans if present Mounting a Verify that the Vyper Drive is properly mounted to the floor or wall f...

Страница 28: ...proper electrical connections as discussed in previous sections The Vyper setup consists of three primary requirements Cooling Loop Fluid Preparation Quantum LX Panel Setup Job FLA Trim Pot Adjustment...

Страница 29: ...ntil the fluid level remains constant about one inch form the top of the manifold See Figure 30 Figure 30 Step 6 Top Off the Cooling System Figure 31 Step 7 Replace the Pipe Plug and Tighten Step 7 Re...

Страница 30: ...fferential pressure the motor speed will increase to meet the capacity requirement When the slide valve reaches the Capacity Control Slide Valve setpoint the motor speed can increase At this point the...

Страница 31: ...r can select either the Vyper or the Har monic Filter setup screens See Figure 35 The flydown menu allows the user to select either theVyper Drive setup or if the Harmonic Filter is installed the disp...

Страница 32: ...aring theVSD memory and resetting the kWh record Standby Time The VSD enters Standby mode when there is no load on the VSD The VSD capacitor banks remain charged and the compressor output is 0 Hz Stan...

Страница 33: ...indicate the status of the field They are displayed as the following 0 no off 1 yes on VSD Operating Mode Harmonic Filter Present Harmonic Filter Operating Mode Water Pump Energized Precharge Relay En...

Страница 34: ...ompressors via the SFS 229 Frick Interface Board This is accomplished through the reception of a Speed Command value in rotations per minute and a Run Command signal from the Quantum LX control panel...

Страница 35: ...on The screen shown in Figure 39 will appear Type 2 into the User Level field Enter Level 2 password Return to the menu and the Home screen The home screen will now provide additional information as s...

Страница 36: ...acity Regulations and Package spe cific information Verify that Screw Compressor with Vyper is selected under the package Drive field This will allow the Vyper specific screens to be displayed See Fig...

Страница 37: ...set to PID Channel 5 Use the table below to program the proper settings Parameter Value Name Drive Cooling Control Running Action Forward Control Point Vyper Coolant Device Source Analog Board 2 Devi...

Страница 38: ...ing the motor and the drive from high currents High Motor Amps Load Inhibit Force Unload Delay Warning 5 SEC Shutdown 5 SEC Applied Motor FLA Calculation IF USE Mtr Nameplate SF 1 0 Mtr Nameplate FLA...

Страница 39: ...Inhibit Applied Motor FLA x 1 1 374 A Force Unload Applied Motor FLA x 1 12 380 A Warning Applied Motor FLA x 1 13 384 A Shutdown Applied Mtr FLA x 1 15 391 A High Motor Amps Load Inhibit 357 Force U...

Страница 40: ...A Shutdown Applied Mtr FLA x 1 15 339 A High Motor Amps Load Inhibit 310 Force Unload 324 Delay Warning 330 5 SEC Shutdown 337 5 SEC Example 4 What are the High Motor Amp setpoints if a 437 HP Vyper...

Страница 41: ...Cycle Time settings and the maximum acceleration rate of 6 08 Hz sec Rate of Decrease The Rate of Decrease parameter set ting determines the speed change step size at which the Vyper will decelerate...

Страница 42: ...wn applications The Variable Speed Minimum Slide Valve Position is a factory default and is related to the Minimum Drive Output setting However an additional control feature is needed to override the...

Страница 43: ...en selecting Setpoints and Compressor Press the ENTER key to advance to the Compressor Safeties Screen Step 2 Refer to Figure 47 Use the cursor arrow and Tab keys to navigate to the Highest Capacity T...

Страница 44: ...re 48 This control strategy is a variation on the generic control strategy described previously Not all applications require or are suitable for the very low speeds obtainable by the Vyper drive Many...

Страница 45: ...proportional component over every 30 sec onds to drive the actual value back to the Capacity Control setpoint If the actual value remains 21 psig the Integration Time Setpoint would increase the drive...

Страница 46: ...2 Motor Service Factor 1 15 3 Multiply Line 1 x Line 2 4 HP Rating of Vyper Drive 5 Vyper Amp Limit If Line 4 is 305 254 HP Value is 380 A If Line 4 is 437 362 HP Value is 565 A 6 Multiply Line 5 x 1...

Страница 47: ...Closed 6 Open 1 Closed 5 Open 4 Open 3 Open Open 2 Open 1 Open FRICK INTERFACE BOARD DIP SWITCH SETTINGS Used before Jan 2008 On the Frick Interface Board Figure 54 on the Vyper right door there is a...

Страница 48: ...ndicators RX TX Logic Board to Quantum LX 8 J16 Communications Cable Logic Board to Quantum LX 9 Communications Indicators RX TX Logic Board to Filter Board 10 J15 Communications Cable Logic Board to...

Страница 49: ...he cooling system and oxidizing the aluminum If any of these conditions exist the coolant may have bacteria growth Take proper health precautions when draining the coolant Drain the coolant and blow t...

Страница 50: ...put current This is due to the power factor at the input to the Vyper being greater than 0 95 and nearly unity when the Harmonic filter option is included Motor FLA must be measured at the motor termi...

Страница 51: ...ick Vyper VYPER ALARMS SHUTDOWNS In addition to the Alarms and Shutdowns that the Quantum LX software generates for the basic compressor package there are warnings and shutdowns that are associated wi...

Страница 52: ...lt 9 Harmonic Filter Logic Board Or Comms Fault 10 Harmonic Filter High Total Demand Distortion 11 High Phase B Inverter Baseplate Temperature 12 High Phase C Inverter Baseplate Temperature 13 Low Pha...

Страница 53: ...ckground message when the chiller is running When this message is displayed all filter related values are unavailable If communications is reestablished normal values will again be displayed If this p...

Страница 54: ...r control board This board monitors the satura tion voltage drop across each IGBT while gated on If the IGBT s saturation voltage exceeds the prescribed limit the gate driver will make the determinati...

Страница 55: ...nput to the logic board can be checked across wires 219 and 220 of the J5 connector of the logic board This message usually means that power to the Vyper was removed If this was not the case check the...

Страница 56: ...24 in the Vyper cabinet Also check to ensure that the serial communications wiring between the micro board and the Interface board andVyper Logic board and the Interface board are connected properly...

Страница 57: ...addition if both temperatures fall below the 37 F limit the unit will trip and the fan s and water pump will be energized This feature provides the Service Dept with a means to run the water pump whi...

Страница 58: ...as Fault 51 except for applying to Phase B Fault 54 Harmonic Filter Phase Locked Loop Message Quantum Fault 54 Quantum LX Harmonic Filter Phase Locked Loop Fault This shutdown indicates that a circui...

Страница 59: ...DC below the filter DC link voltage setpoint The filter DC link voltage setpoint is determined by the filter logic board via the sensing of the three phase input line to line voltage This setpoint is...

Страница 60: ...t to the initial speed command and the Motor Current is monitored every two seconds If the Motor Current rises above 103 the unit enters current limit and a warning condition will be set Thereafter as...

Страница 61: ...RD 639A0211H25 FUSES VOLTAGE TRANSIENT BOARD 639A0211H26 SCR TRIGGER BD 60 HZ 639A0211H27 SCR TRIGGER BD 50 HZ 639A0211H28 VSD DC BALANCING RESISTOR 639A0211H29 COOLANT PUMP 639A0211H30 BUS SNUBBER CA...

Страница 62: ...HZ 639A0211H27 SCR TRIGGER BD 50 HZ 639A0211H28 VSD DC BALANCING RESISTOR 639A0211H29 COOLANT PUMP 639A0211H30 BUS SNUBBER CAPACITOR 639A0211H31 SNUBBER RESISTOR 639A0211H32 SHELL TUBE HEAT EXCHANGER...

Страница 63: ...FILTER RETROFIT 50HZ 639A0211H59 FILTER POWER MODULE COMPLETE KIT 639A0211H66 HARMONIC FILTER SPARE PARTS LISTS1 MODEL 437 Part Description Frick Part BUS ISOLATOR BOARD 639A0211H42 BUS PLATE KIT 639...

Страница 64: ...gh DC Bus Voltage 58 Harmonic Filter Precharge Low DC Bus Voltage 58 Harmonic Filter Run Signal 59 Harmonic Filter Serial Communication 60 High Converter Heat Sink Temperature 56 High DC Current Bus V...

Страница 65: ...URE CONTROL VALVE WIRING 24 transducers 10 WIRING ENTRY LOCATIONS 21 Insulated Gate Bipolar Transistor 12 Integration Time Setpoint 45 Interface board 53 inverter module base plate 56 J Job FLA 46 57...

Страница 66: ...upply Contactor 34 Supply Current 33 Total Demand Distortion 33 Total Harmonic Distortion 33 Total kWh 33 Vyper Level 2 Screen 47 Vyper Level 2 screen 46 Vyper Amp Limit 40 Quantum LX Control panel 3...

Страница 67: ...100 200 IOM FEB 09 Page 67 VYPER VARIABLE SPEED DRIVE NOTES...

Страница 68: ...System integration is what we do Q NET supports open protocols for SCADA systems i e Allen Bradley DF1 Modbus RTU Modbus ASCII and Industrial Ethernet Protocols Q NET connects instantly for local or...

Отзывы: