background image

070.655-IOM (FEB 22)

Page 17

SBTP Rotary Screw Compressor

Installation

shaft and motor shaft to allow for seal removal. See 
the relevant outline drawings in 

Figure 3 

to 

Figure 12

.

•   The coupling must be able to take up any misalignment 

between motor and compressor. It is critical to the life 
of the shaft seal that misalignment is kept to the mini-
mum possible value. Ensure you follow the coupling 
manufacturer’s guidelines for checking and correcting 
any misalignment. 

Aligning the coupling

You must perform a coupling alignment before start-up: 

1.   After installing the compressor on the job site, check 

the alignment again and correct if necessary before 
start-up. 

2.   After a few hours operation, check the alignment while 

the package is still hot. Correct hot alignment is criti-
cal to ensure the life of the shaft seal and compressor 
bearings.

Note:

 The maximum radial runout is 0.004 in. total indica-

tor reading. The maximum axial runout is 0.004 in. 

total indicator reading. 

3.   Use a dial indicator or another appropriate measuring 

device to determine the total indicator runout. 

4.   Check the indicator bracket sag because all brackets 

have some flexibility. The best way to measure this is 

as follows:
a.  Attach the dial indicator and bracket on a pipe at the 

coupling span distance. 

b. Zero the indicator in the 12:00 position.
c.  Rotate the pipe so the indicator is in the 6:00  

position. The reading on the indicator in the 6:00 
position is the bracket sag. 

You must include this value in the dial indicator readings 

when affixed to the coupling for an accurate alignment.

Oil heaters

Your package must be equipped with oil heaters that 

provide sufficient heat to prevent condensation from oc

-

curring during shutdown cycles. In addition, Frick strongly 
suggests heat tracing for all of the lube oil lines includ-

ing oil filters and the oil cooler. Activate the heat tracing 

during compressor shutdown to ensure that all of the lube 
system is up to the correct temperature before startup. 

Oil filters 

Using filter elements other than Johnson Controls-Frick 

must be approved in writing by Johnson Controls-Frick 
engineering or a warranty claim may be denied. Typical 

oil filter specification  

β

5 = 75 according to ISO 4572 is 

required to obtain the recommended oil cleanliness class 
16/14/11 according to ISO 4406.

Oil cooling requirements

Compressor oil needs to be cooled to control the discharge 
temperature, maintain the appropriate oil viscosity, and to 
preserve the life of the oil. Normally the discharge tempera-
ture is between 170°F to 180°F. See CoolWare

 to determine 

your configuration. 

The main oil injection line that is connected to port SM1 must 

have a regulating valve to permit adjustment of the oil flow to 

maintain the appropriate discharge temperature at all times.

Frick suggests using a three-way mixing valve to keep the 
oil temperature in the normal range of 120°F to 140°F. 
The valve provides warm oil to the compressor quickly, re-
ducing the pressure drop caused by cold, viscous oil. This 

ensures the correct oil flow and temperature over the full 

range of operating conditions.

While liquid injection oil cooling is an option for anti-
friction Frick screw compressors, it is not recommended 
for compressors supplied with tilting pad thrust bearings. 
Acceptable methods of oil cooling would use either water, 
air, or refrigerant cooled oil coolers.

Natural gas applications

One application that usually requires higher discharge 
temperatures, as high as 250°F, is natural gas gathering at 
the wellhead. Moisture is normally present in the gas and 
it is imperative that the discharge temperature be at least 
30°F higher than the discharge dew point temperature for 
the gas. 

1.   Open CoolWare and from the 

Wet/Dry Mode

 list, se-

lect 

Water Saturated

2.   Select 

Calculate

 to get the discharge dew point tem-

perature for your application. 

Oil temperatures as high as 170°F can be used to achieve 
the necessary discharge temperature to prevent moisture 
from condensing in the oil separator. Contact Johnson 
Controls–Frick for additional information for natural gas 
compression.

Dehydration or evacuation test

Evacuate the system to 1000 microns. Valve off the 
vacuum pump and hold vacuum for 1 h. 

Pass:

 vacuum cannot rise more than 500 microns during  

1 h hold period.

Fail

: vacuum rise is more than 500 microns during 1 h 

hold period. Identify and repair any system leaks. Repeat 
vacuum test until requirements are met.

Содержание SBTP 355 Series

Страница 1: ...ctions may result in personal injury or death damage to the unit or incorrect operation Rotary Screw Compressor SBTP 355 and 408 Series Form 070 655 IOM FEB 2022 Installation Operation Maintenance Fil...

Страница 2: ...enance General information 21 Normal maintenance operations 21 General maintenance 21 Changing the oil 21 Maintenance program 21 Maintenance schedule 22 Vibration analysis 22 Oil quality and analysis...

Страница 3: ...It is necessary to keep the discharge temperature high enough to prevent condensation of any moisture in the compressor and oil separator Design limitations Frick compressors are designed for operatio...

Страница 4: ...capacity sleeve bearings to carry radial loads at both the inlet and outlet ends of the compressor Heavy duty tilt pad thrust bearings mounted at the discharge end of the compressor to carry axial lo...

Страница 5: ...vely The cylindrical sleeve bearings are oil grooved for optimal lubrication and higher radial load capability The tilting pad thrust bearing uses offset pads and directed lubrication to minimize powe...

Страница 6: ...070 655 IOM FEB 22 Page 6 SBTP Rotary Screw Compressor Installation Operation Maintenance This page is intentionally left blank...

Страница 7: ...tion Do not exceed the rotor and bearing design set limitations of any compressor Refer to CoolWare for more information Outline dimensions See Figure 3 to Figure 12 for port locations Drawings are fo...

Страница 8: ...e 4 SBTP 355 compressor port locations view A A Suction 3511 compressor 10 300 ANSI flange 1 in 8 UNC 2B x 2 13 DP Proximity sensor phase probe 4X radial bearing RTD 4X proximity sensor vertical probe...

Страница 9: ...9 SBTP Rotary Screw Compressor Installation Figure 5 SBTP 355 compressor port locations view B B Figure 6 SBTP 355 compressor port locations view C C Axial bearing RTD Axial bearing RTD 2x Axial beari...

Страница 10: ...llation SC 15 SC 5 ST 1 SM 1 SC 9 SV 1 SC 6 ST 2 Figure 8 SBTP 408 compressor port locations SD 1 Discharge 10 in 300 ANSI flange 1 in 8 UNC 2B x 2 25 DP Standard piping arrangement View D D View E E...

Страница 11: ...X proximity sensor vertical probe 2X proximity sensor phase probe Suction compressors 4018 and 4021 16 in 400 ANSI flange 1 1 4 7 UNC 2B x 2 56 DP 20X on 22 500 B C Compressor 4013 12 in 400 ANSI flan...

Страница 12: ...ion SC 10 SC 11 Axial bearing RTD Axial bearing RTD Axial bearing RTD View C C Figure 11 SBTP 408 compressor port locations view C C Axial bearing RTD View E E View D D T SL 1 SC 3 SC 2 SL 2 P Dischar...

Страница 13: ...suction pressure SC 13 1 1 16 12 UN 2B straight thread o ring 980A0013K64 Inlet bearing drain suction pressure P 3 4 16 UNF 2B straight thread o ring 980A0013K60 Cylinder pressure manifold block pres...

Страница 14: ...g 980A0013K60 Drain suction pressure P 3 4 16 UNF 2B straight thread o ring 980A0013K60 Cylinder pressure manifold block pressure T 3 4 16 UNF 2B straight thread o ring 980A0013K60 Cylinder vent manif...

Страница 15: ...e or forklift by hooking into the two lifting rings at each end of the main housings Only use the compressor lifting rings to lift the compressor itself See the following figure Figure 13 Lifting ring...

Страница 16: ...ecific Frick oil for the refrigerant being used Depending on the application a different oil can be selected provided it is of the correct viscosity and is compatible with the refrigerant and compress...

Страница 17: ...gineering or a warranty claim may be denied Typical oil filter specification 5 75 according to ISO 4572 is required to obtain the recommended oil cleanliness class 16 14 11 according to ISO 4406 Oil c...

Страница 18: ...t and ensure design limitations are not exceeded Connect to and signal as shown in the Figure 17 For compressor panel instructions refer to the latest Quantum Controller Operations currently 090 070 O...

Страница 19: ...he compressor unloads when SV solenoid YY1 is energized and oil flows from the oil manifold through valve ports P and A to cylin der port SC1 and enters the unload side of the cylinder Si multaneously...

Страница 20: ...nd during initial start up 1 For effective and safe operation the compressor must be run at the correct speed and discharge pressure Exceeding design conditions creates a potential hazard 2 After 1 h...

Страница 21: ...without shutting down the package Avoid slugging the compressor with liquids oil while screw compressors are probably the most tolerant of any compressor type available today about ingestion of some...

Страница 22: ...ngs Oil quality and analysis High quality and suitable oil is necessary to ensure com pressor longevity and reliability Oil quality rapidly dete riorates in systems containing moisture and air or othe...

Страница 23: ...ems on the list are possible causes and which items are additional symptoms High discharge temperature and high oil temperature readings on a display may both be symp toms of a problem and not causall...

Страница 24: ...n until steady state conditions are met Shut down lock out motor starter and per form a hot alignment Long term storage For long term storage of 6 months to 5 years provisions are required regardless...

Страница 25: ...ged pressurize to be tween 5 psig to 15 psig with nitrogen See the following table for the amounts of oil needed for each compressor Table 8 Necessary oil volume Model Oil volume gal 3511 77 3515 94 3...

Страница 26: ...al problem is suspected contact Johnson Controls Frick Service Do not attempt to disassemble compressor Troubleshooting the oil pump and system Problem Cause Solution Pump does not produce enough oil...

Страница 27: ...he valve is functioning mechanically To actuate the solenoid mechanically insert a piece of 3 16 in rod against the armature pin and push the spool to the opposite end Push A side to confirm unload ca...

Страница 28: ...all high voltage wiring __ Confirm all 120 V control wiring is run in a separate conduit from compressor motor wiring __ Confirm no high voltage wiring enters the control panel at any point __ Check...

Страница 29: ...nter checked Marked N A Compressor coupling hub runout Motor coupling hub runout Initial cold alignment Initial hot alignment Final hot alignment Operating log sheet Date Time Hour meter reading Equip...

Страница 30: ...Manufacturer and size of coupling Motor manufacturer Motor serial number RPM Frame size H P Refrigerant Ambient room temperature F Operating conditions Date Sales order number End user Installing cont...

Страница 31: ...mil pk pk Compressor drive end male X and Y X ____ ____ mil pk pk Y ____ ____ mil pk pk Compressor non drive end female X and Y X ____ ____ mil pk pk Y ____ ____ mil pk pk Male axial displacement push...

Страница 32: ...p 5 slide valve 4 5 18 23 slide valve transmitter 18 solenoids 18 solenoid valves 19 start up 20 storage 15 suction accumulator 21 suction pressure 23 suction strainer 20 21 system piping 23 Index A a...

Страница 33: ...l pressure regulator 26 piston seals 26 pressure regulating valve 26 pump 26 pump strainer 26 service valves 26 slide stop 26 slide stop indicator rod 26 slide valve 26 solenoid coils 27 solenoid spoo...

Страница 34: ...nesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com Frick Form 070 655 IOM 2022 02 Supersedes 070 655 IOM 2019 05 Subject to change without notice Published in USA 02...

Отзывы: