QUANTUM™ HD UNITY SYSTEM CONTROLLER
MAINTENANCE
090.670-M (APR 2020)
Page 24
Table 9: Ethernet Connector (J27) LED Definitions
Amber
LED
Green
LED
Link state
Off
Off
No link established
1000 Mbps ( 1 Gigabit)
On
Off
No activity
Blinking
Off
Activity
100 Mbps
Off
On
No activity
Off
Blinking
Activity
10 Mbps
On
On
No activity
Blinking
Blinking
Activity
Table 10: Power Connector Pinout (J37)
Pin
Function
1
Ground (GND)
2
Ground (GND)
3
9 V - 28 V
(VCC)
4
9 V -28 V
(VCC)
Reset IP Address to Default
Reset a panel IP address to a known default per the fol-
lowing procedure:
1. Power off the panel
2. Set DIP switch (J11) number 2 to the ON position
3. Power up the panel and wait until the panel restarts
4. Set DIP switch (J11) number 2 to the OFF position
After the above procedure, the IP address is reset to the
default address for the corresponding Unity product:
Compressor
192.168.0.170
Condenser / Vessel
192.168.0.171
Evaporator
192.168.0.172
Engine
Room
192.168.0.173
Содержание QUANTUM HD UNITY
Страница 10: ...QUANTUM HD UNITY SYSTEM CONTROLLER MAINTENANCE 090 670 M APR 2020 Page 10 This page is intentionally left blank...
Страница 26: ...QUANTUM HD UNITY SYSTEM CONTROLLER MAINTENANCE 090 670 M APR 2020 Page 26 This page is intentionally left blank...
Страница 27: ...QUANTUM HD UNITY SYSTEM CONTROLLER MAINTENANCE 090 670 M APR 2020 Page 27 SECTION 4 DIGITAL BOARD...
Страница 41: ...QUANTUM HD UNITY SYSTEM CONTROLLER MAINTENANCE 090 670 M APR 2020 Page 41 SECTION 5 ANALOG BOARD...
Страница 51: ...QUANTUM HD UNITY SYSTEM CONTROLLER MAINTENANCE 090 670 M APR 2020 Page 51 SECTION 6 SERVICE SCREENS...
Страница 60: ...QUANTUM HD UNITY SYSTEM CONTROLLER MAINTENANCE 090 670 M APR 2020 Page 60 This page is intentionally left blank...