![Frecon FR500-4T-0.7G/1.5PB Скачать руководство пользователя страница 144](http://html1.mh-extra.com/html/frecon/fr500-4t-0-7g-1-5pb/fr500-4t-0-7g-1-5pb_user-manual_2329263144.webp)
FR500A&FR510A Series Vector Control Inverter
- 144 -
It is mainly used to adjust the phase between the given and feedback when it is used with the
"forward position offset enablement" and "reverse position offset enablement" terminals. When the
position is synchronized, if the "positive position offset enable" terminal is valid, the phase of the
converter control motor will gradually change along the positive direction; if the "direction position
offset enable" terminal is valid, the phase of the converter control motor will gradually change along
the reverse direction.
Group F22 Virtual IO
F22.00
Terminal function selection of
virtual VDI1
Range: same as F04.00
Default: 0
F22.01
Terminal function selection of
virtual VDI2
Range: same as F04.00
Default: 0
F22.02
Terminal function selection of
virtual VDI3
Range: same as F04.00
Default: 0
F22.03
Terminal function selection of
virtual VDI4
Range: same as F04.00
Default: 0
F22.04
Terminal function selection of
virtual VDI5
Range: same as F04.00
Default: 0
Virtual VDI1~VDI2 can be used as multifunctional digital input, they are set as common DI
F22.05
Valid status setting
mode of virtual
terminals
Range: 00000
~
11111
Default: 00000
F22.06
Setting status of virtual
VDI terminals
Range: 00000
~
11111
Default: 00000
There are two modes to set status of virtual VDI terminal, and selected by F22.05
0:the validity of VDI depends on validity of VDO output, and VDOx uniquely bound with VDOx(x
range 1-5)
1:Binary digit of F22.06 determine the status of virtual terminal respectively
F22.07
Selection of virtual
VDO1 output function
0:internal short circuited
physics Dix
Other: The same as F05.00
Default: 0
F22.08
Selection of virtual
VDO2 output function
0:internal short circuited
physics Dix
Other: The same as F05.00
Default: 0
F22.09
Selection of virtual
VDO3 output function
0:internal short circuited
physics Dix
Other: The same as F05.00
Default: 0
F22.10
Selection of virtual
VDO4 output function
0:internal short circuited
physics Dix
Other: The same as F05.00
Default: 0
F22.11
Selection of virtual
VDO5 output function
0:internal short circuited
physics Dix
Other: The same as F05.00
Default: 0
0:Output status of VDO1~VDO5 determined by input status of DI1~DI5 on the control board, at
this situation, there is a one-one correspondence between VD0x and Dix.
F22.12
Virtual VDO1 output
delay time
Range: 0.0s
~
6000.0s
Default: 0.0s
F22.13
Virtual VDO2 output
delay time
Range: 0.0s
~
6000.0s
Default: 0.0s
F22.14
Virtual VDO3 output
delay time
Range: 0.0s
~
6000.0s
Default: 0.0s
F22.15
Virtual VDO4 output
delay time
Range: 0.0s
~
6000.0s
Default: 0.0s
F22.16
Virtual VDO5 output
delay time
Range: 0.0s
~
6000.0s
Default: 0.0s
F22.17
Positive and negative
logic of VD0 output
terminal
Range: 00000
~
11111
Default: 00000