FR500A&FR510A Series Vector Control Inverter
- 123 -
Unit’s place: Overspeed Action Selection
0:Report error and coast to stop
1:Warning and ramp to stop
2: Alarm and continue run with failure frequency
3:No protection
Ten’s place: Selection of Excessive Speed Deviation(same as Unit’s place)
F11.41
Overspeed detection value
Range: 0.0
~
150.0%
Default : 120.0%
F11.42
Overspeed detection time
Range: 0.0
~
60.0s
Default : 1.0s
This function is only valid when the frequency converter runs with speed sensor vector control.
When the inverter detects that the actual speed of the motor exceeds the maximum frequency *
over-speed detection value F11.41, and the duration is longer than the over-speed detection time
F11.42, the converter fault alarm Err37, which is processed according to the fault protection action
F11.40 mode.
When the overspeed detection time is 0.0s, the overspeed fault detection is cancelled.
F11.43
Detection value of excessive
velocity deviation
Range: 0.0
~
50.0%
Default : 20.0%
F11.44
Detection time of excessive
velocity deviation
Range: 0.0
~
60.0s
Default : 5.0s
This function is only valid when the frequency converter runs with speed sensor vector control.
When the inverter detects that the actual speed of the motor deviates from the set frequency, the
deviation is greater than the detection value F11.43 of the speed deviation, and the duration is longer
than the detection time F11.44 of the speed deviation, the frequency converter fault alarm Err38 is
processed according to the fault protection action F11.40 mode.
When the detection time of speed deviation is 0.0s, the fault detection of speed deviation is
cancelled.
Group F12 Multi-Reference and Simple PLC Function
F12.00
Reference 0
Range:-100.0
~
100.0%
Default:0.0%
F12.01
Reference 1
Range:-100.0
~
100.0%
Default:0.0%
F12.02
Reference 2
Range:-100.0
~
100.0%
Default:0.0%
F12.03
Reference 3
Range:-100.0
~
100.0%
Default:0.0%
F12.04
Reference 4
Range:-100.0
~
100.0%
Default:0.0%
F12.05
Reference 5
Range:-100.0
~
100.0%
Default:0.0%
F12.06
Reference 6
Range:-100.0
~
100.0%
Default:0.0%
F12.07
Reference 7
Range:-100.0
~
100.0%
Default:0.0%
F12.08
Reference 8
Range:-100.0
~
100.0%
Default:0.0%
F12.09
Reference 9
Range:-100.0
~
100.0%
Default:0.0%
F12.10
Reference 10
Range:-100.0
~
100.0%
Default:0.0%
F12.11
Reference 11
Range:-100.0
~
100.0%
Default:0.0%
F12.12
Reference 12
Range:-100.0
~
100.0%
Default:0.0%
F12.13
Reference 13
Range:-100.0
~
100.0%
Default:0.0%
F12.14
Reference 14
Range:-100.0
~
100.0%
Default:0.0%
F12.15
Reference 15
Range:-100.0
~
100.0%
Default:0.0%
At most 16 steps of multi-reference can be set by different status combinations of "
multi-reference terminals 1
~
4" of digital input.
Multi-reference can be the setting source of frequency, V/F separated voltage and process PID.
The multi-reference is relative value and ranges from -100.0% to 100.0%.
As frequency source, it is a percentage relative to the maximum frequency. As V/F separated
voltage source, it is a percentage relative to the rated motor voltage. As process PID setting source, it
does not require conversion.
Multi-reference can be switched over based on different states of DI terminals. For details, see the
descriptions of group F4.
F12.16
Reference 0 source
Range:0
~
6
Default: 0
0: Digital setting
(
F12.00)